Lightning Protection MCQs — Set 8
10 practice questions on surge protection coordination, with answers and explanations. Work each one out before checking the answer.
Q1. For a Class I lightning protection system, what is the rolling-sphere radius?
- (a) 20 m
- (b) 30 m
- (c) 45 m
- (d) 60 m
Answer: (a) 20 m — the rolling-sphere radii are 20 m for Class I, 30 m for Class II, 45 m for Class III and 60 m for Class IV; the smaller the sphere, the higher the protection level.
Q2. Where is a Type I SPD normally installed?
- (a) At the socket outlet next to a computer
- (b) At the service entrance, on the main incomer
- (c) On the roof, next to the air terminal
- (d) Underground, next to the earth rod
Answer: (b) At the service entrance, on the main incomer — the Type I SPD is the first line of defence and must handle the largest share of a direct lightning current entering through the supply lines.
Q3. Where is a Type II SPD normally installed?
- (a) At a distribution board or sub-distribution board
- (b) On the lightning rod
- (c) At the earth electrode
- (d) Inside the electricity meter only
Answer: (a) At a distribution board or sub-distribution board — Type II SPDs protect the circuits fed from that board against induced surges that get past the Type I device.
Q4. Where is a Type III SPD normally installed?
- (a) At the main incomer
- (b) On the down conductor
- (c) Close to sensitive equipment, such as at a socket outlet
- (d) On the roof mesh
Answer: (c) Close to sensitive equipment, such as at a socket outlet — Type III SPDs give fine protection to individual appliances and must sit near the equipment they protect.
Q5. What does coordination of SPDs mean?
- (a) All SPDs are the same type
- (b) The Types I, II and III are staged so each one takes its share of the surge energy in turn
- (c) SPDs are connected in parallel with the earth rod
- (d) Only one SPD is used per building
Answer: (b) The Types I, II and III are staged so each one takes its share of the surge energy in turn — without coordination, the smallest SPD could try to take the whole surge and fail, so the stages must be matched.
Q6. What does an SPD do to the excess voltage of a surge?
- (a) It stores the voltage in a battery
- (b) It diverts the surge current to earth and clamps the voltage to a safe level
- (c) It sends the voltage back to the supply
- (d) It converts the voltage into heat in the wiring
Answer: (b) It diverts the surge current to earth and clamps the voltage to a safe level — during normal operation the SPD does nothing, but when the voltage rises above its threshold it conducts the surge away.
Q7. Why is an SPD still needed in a building that already has an external lightning protection system?
- (a) The external system only protects the roof
- (b) The external system handles the direct strike, but surges can still enter through power and data lines and need an SPD
- (c) SPDs replace the down conductors
- (d) The external system increases the surge voltage
Answer: (b) The external system handles the direct strike, but surges can still enter through power and data lines and need an SPD — external and internal protection work together: rods and conductors for the direct strike, SPDs for the surges that travel along wires.
Q8. Which test waveform is used for a Type I SPD, which must handle direct lightning current?
- (a) 8/20 µs
- (b) 10/350 µs
- (c) 1.2/50 µs
- (d) 50/60 Hz sine wave
Answer: (b) 10/350 µs — Type I SPDs are tested with the 10/350 µs impulse current waveform, which represents the long-duration current of a direct lightning strike.
Q9. Which test waveform is used for a Type II SPD, which must handle induced surges?
- (a) 10/350 µs
- (b) 8/20 µs
- (c) 1.2/50 µs
- (d) 50/60 Hz sine wave
Answer: (b) 8/20 µs — Type II SPDs are tested with the 8/20 µs impulse current waveform, which represents the shorter induced surges that travel along power lines.
Q10. Where should an SPD be installed in relation to the equipment it protects?
- (a) As far away as possible
- (b) As close as possible, and upstream of the equipment
- (c) On the roof
- (d) In a different building
Answer: (b) As close as possible, and upstream of the equipment — long leads between the SPD and the equipment add voltage during a surge, so short connections keep the protection effective.