Lightning Protection MCQs — Set 7
10 practice questions on bonding and equipotential bonding, with answers and explanations. Work each one out before checking the answer.
Q1. Why are metal services such as water and gas pipes bonded to the lightning protection system?
- (a) To make the pipes stronger
- (b) To equalise potentials and prevent dangerous sparking between the pipe and the lightning conductors
- (c) To reduce the earth resistance
- (d) To stop the pipes from rusting
Answer: (b) To equalise potentials and prevent dangerous sparking between the pipe and the lightning conductors — during a strike the conductors rise to a high voltage, and an unbonded pipe at a different voltage can receive a spark.
Q2. What is equipotential bonding?
- (a) Connecting all conductive parts together so no voltage difference appears between them
- (b) Connecting every conductor to a separate earth rod
- (c) Insulating all metal parts from each other
- (d) Measuring the voltage between two points
Answer: (a) Connecting all conductive parts together so no voltage difference appears between them — if everything rises and falls together, there is no voltage to drive a spark between parts.
Q3. What is side flashing in lightning protection?
- (a) A flash of light from the strike
- (b) A spark jumping from a lightning conductor to a nearby metal object when the separation is too small
- (c) A warning light on the surge protector
- (d) The reflection of lightning in a window
Answer: (b) A spark jumping from a lightning conductor to a nearby metal object when the separation is too small — side flashing is a fire and shock hazard, and it is prevented by keeping enough separation distance or by bonding.
Q4. What is the separation distance in a lightning protection system?
- (a) The distance between two buildings
- (b) The minimum distance between a lightning conductor and other metal parts needed to avoid flashover
- (c) The length of the down conductor
- (d) The depth of the earth electrode
Answer: (b) The minimum distance between a lightning conductor and other metal parts needed to avoid flashover — if the separation distance cannot be kept, the metal part must be bonded to the lightning protection system instead.
Q5. Which items should be bonded to the lightning protection system at ground level?
- (a) Only the down conductors
- (b) Gas and water pipes, cable sheaths and structural steel
- (c) Only the air terminals
- (d) Only plastic pipes
Answer: (b) Gas and water pipes, cable sheaths and structural steel — all incoming conductive services are bonded so they share the same potential as the lightning protection system during a strike.
Q6. Why is bonding also needed at roof level?
- (a) Roof metalwork such as vents and air-conditioning units sits close to air terminals and down conductors
- (b) The roof is the only place lightning strikes
- (c) Bonding at roof level replaces the earth electrode
- (d) It makes the roof waterproof
Answer: (a) Roof metalwork such as vents and air-conditioning units sits close to air terminals and down conductors — anything metal on the roof that lightning conductors pass near must be bonded or kept at the separation distance.
Q7. What is the danger if a metal water pipe inside a building is not bonded to the lightning protection system?
- (a) The pipe will rust faster
- (b) A dangerous potential difference can appear between the pipe and the lightning conductors, causing sparking
- (c) The water pressure will drop
- (d) The pipe will attract lightning
Answer: (b) A dangerous potential difference can appear between the pipe and the lightning conductors, causing sparking — a spark inside a building can start a fire or give a person touching the pipe a shock.
Q8. What material is normally used for bonding conductors?
- (a) Copper
- (b) Plastic
- (c) Rubber
- (d) Wood
Answer: (a) Copper — copper bonding conductors give a low-resistance connection that can carry the share of lightning current that flows during a strike.
Q9. When is the separation distance most critical?
- (a) On short, single-storey buildings
- (b) On tall structures and long down conductors, where the voltage along the conductor is highest
- (c) On buildings with no metalwork
- (d) Only in dry weather
Answer: (b) On tall structures and long down conductors, where the voltage along the conductor is highest — the longer the current path, the greater the voltage rise, so more separation (or bonding) is needed.
Q10. Why is it dangerous to touch a down conductor while lightning is striking?
- (a) The conductor is hot from the sun
- (b) The conductor carries the strike current and its voltage rises sharply, so touching it can give a lethal shock
- (c) The conductor is slippery when wet
- (d) The conductor may fall off the wall
Answer: (b) The conductor carries the strike current and its voltage rises sharply, so touching it can give a lethal shock — even a 30 kA stroke through a 10 Ω earth path raises the system by 300 kV, so nobody should be near a down conductor during a storm.