Lightning Protection MCQs — Set 5

10 practice questions on the rolling sphere method and lightning protection levels, with answers and explanations. Work each one out before checking the answer.

Q1. What is the rolling sphere radius for Lightning Protection System Class I?

  • (a) 10 m
  • (b) 20 m
  • (c) 45 m
  • (d) 60 m

Answer: (b) 20 m — Class I, the highest protection level, uses the smallest rolling sphere radius of 20 m.

Q2. What is the rolling sphere radius for Lightning Protection System Class II?

  • (a) 20 m
  • (b) 30 m
  • (c) 45 m
  • (d) 60 m

Answer: (b) 30 m — Class II uses a rolling sphere radius of 30 m.

Q3. What is the rolling sphere radius for Lightning Protection System Class III?

  • (a) 20 m
  • (b) 30 m
  • (c) 45 m
  • (d) 60 m

Answer: (c) 45 m — Class III uses a rolling sphere radius of 45 m.

Q4. What is the rolling sphere radius for Lightning Protection System Class IV?

  • (a) 20 m
  • (b) 30 m
  • (c) 45 m
  • (d) 60 m

Answer: (d) 60 m — Class IV, the lowest protection level, uses the largest rolling sphere radius of 60 m.

Q5. What does the rolling sphere method determine?

  • (a) The length of the down conductors
  • (b) Which parts of a structure lightning can strike, by rolling an imaginary sphere over it
  • (c) The resistance of the earth electrode
  • (d) The size of the surge protector

Answer: (b) Which parts of a structure lightning can strike, by rolling an imaginary sphere over it — any point the sphere touches is a possible strike point and needs an air terminal; points the sphere cannot reach are protected.

Q6. Which lightning protection class gives the highest level of protection?

  • (a) Class I
  • (b) Class II
  • (c) Class III
  • (d) Class IV

Answer: (a) Class I — Class I is the strictest level, with the smallest rolling sphere radius (20 m) and the closest down-conductor spacing.

Q7. A larger rolling sphere radius corresponds to which level of protection?

  • (a) A higher level of protection
  • (b) A lower level of protection
  • (c) The same level of protection
  • (d) Protection against surges only

Answer: (b) A lower level of protection — a bigger sphere (60 m for Class IV) touches fewer points on the structure, so fewer air terminals are needed but the protection is less strict.

Q8. What is a lightning protection level (LPL)?

  • (a) The height of the air terminal
  • (b) A set of lightning current values that the protection system is designed to handle, with a stated probability
  • (c) The number of down conductors
  • (d) The voltage of the surge protector

Answer: (b) A set of lightning current values that the protection system is designed to handle, with a stated probability — each level (I to IV) defines maximum and minimum lightning currents the system must intercept and carry safely.

Q9. Which rolling sphere radius is smaller: Class I or Class II?

  • (a) Class I, at 20 m against 30 m for Class II
  • (b) Class II, at 20 m against 30 m for Class I
  • (c) They are equal, both 30 m
  • (d) Class I, at 30 m against 45 m for Class II

Answer: (a) Class I, at 20 m against 30 m for Class II — the smaller sphere of Class I reaches into more gaps, so more of the structure must be covered by air terminals.

Q10. When is the rolling sphere method especially useful?

  • (a) Only on single-storey houses
  • (b) On complex or large structures where the protective angle method alone is not enough
  • (c) Only for measuring earth resistance
  • (d) Only on metal roofs

Answer: (b) On complex or large structures where the protective angle method alone is not enough — the rolling sphere can be applied to any shape of building, including ones with irregular roofs and tall features.