Q1. What earth resistance is commonly targeted for a lightning protection earth electrode?
- (a) 100 Ω or less
- (b) 50 Ω or less
- (c) 10 Ω or less
- (d) 1 Ω or less
Answer: (c) 10 Ω or less — a lightning protection earth electrode is commonly targeted at 10 Ω or less so the strike current can disperse into the ground without a huge voltage rise.
Q2. A 30 kA lightning stroke flows through an earth electrode of 10 Ω resistance. What is the voltage rise at the electrode?
- (a) 3 kV
- (b) 30 kV
- (c) 300 kV
- (d) 3,000 kV
Answer: (c) 300 kV — V = I × R = 30,000 A × 10 Ω = 300,000 V = 300 kV, which shows why a low earth resistance matters.
Q3. A 20 kA lightning stroke flows through an earth electrode of 10 Ω resistance. What is the voltage rise at the electrode?
- (a) 20 kV
- (b) 200 kV
- (c) 2,000 kV
- (d) 2 kV
Answer: (b) 200 kV — V = I × R = 20,000 A × 10 Ω = 200,000 V = 200 kV.
Q4. A 30 kA lightning stroke flows through an earth electrode of 5 Ω resistance. What is the voltage rise at the electrode?
- (a) 6 kV
- (b) 60 kV
- (c) 150 kV
- (d) 600 kV
Answer: (c) 150 kV — V = I × R = 30,000 A × 5 Ω = 150,000 V = 150 kV, half the rise of a 10 Ω electrode for the same stroke.
Q5. What is a common type of earth electrode used in lightning protection?
- (a) A copper-clad steel rod driven vertically into the ground
- (b) A plastic pipe filled with water
- (c) A wooden stake
- (d) A rubber mat on the surface
Answer: (a) A copper-clad steel rod driven vertically into the ground — the steel gives strength for driving, and the copper coating gives conductivity and corrosion resistance.
Q6. What is a ring earth electrode?
- (a) A single rod under the building
- (b) A conductor buried in a ring around the building, connected to all the down conductors
- (c) A circular air terminal on the roof
- (d) A surge protector shaped like a ring
Answer: (b) A conductor buried in a ring around the building, connected to all the down conductors — the ring spreads the strike current over a large area and keeps all the down conductors at a similar potential.
Q7. Why does dry soil increase the resistance of an earth electrode?
- (a) Dry soil is heavier
- (b) Less moisture means fewer dissolved ions to carry current, so the soil resistivity is higher
- (c) Dry soil damages the copper
- (d) Dry soil pushes the rod out of the ground
Answer: (b) Less moisture means fewer dissolved ions to carry current, so the soil resistivity is higher — electrodes in dry, sandy or rocky ground often need to be longer, deeper or more numerous to reach the target resistance.
Q8. How is the resistance of an earth electrode normally measured?
- (a) With a clamp meter on the down conductor
- (b) With an earth resistance tester using the fall-of-potential method
- (c) With a voltmeter across the air terminal
- (d) By counting the down conductors
Answer: (b) With an earth resistance tester using the fall-of-potential method — the tester injects a current into the electrode and measures the voltage rise at a probe, with the test joint opened to isolate the electrode.
Q9. Why should the separate earth electrodes of a lightning protection system be bonded together?
- (a) To increase the total earth resistance
- (b) To avoid dangerous potential differences between electrodes during a strike
- (c) To save on copper
- (d) To make the electrodes easier to find
Answer: (b) To avoid dangerous potential differences between electrodes during a strike — bonded electrodes rise in voltage together, so no spark can jump between different parts of the system.
Q10. What is soil resistivity?
- (a) The weight of one cubic metre of soil
- (b) The resistance of a unit volume of soil, which decides how well an earth electrode will perform
- (c) The depth of the topsoil layer
- (d) The amount of water in the soil
Answer: (b) The resistance of a unit volume of soil, which decides how well an earth electrode will perform — low-resistivity soil (damp clay) gives a low electrode resistance, while high-resistivity soil (dry rock) gives a high one.