Lightning Protection MCQs — Set 3

10 practice questions on down conductors, with answers and explanations. Work each one out before checking the answer.

Q1. What is the purpose of a down conductor in a lightning protection system?

  • (a) To attract lightning to the building
  • (b) To carry the lightning current from the air terminal safely to the earth electrode
  • (c) To measure the earth resistance
  • (d) To protect appliances from surges

Answer: (b) To carry the lightning current from the air terminal safely to the earth electrode — the down conductor is the low-impedance path that keeps the strike current away from the building fabric.

Q2. A building has a perimeter of 60 m and needs Class I lightning protection, with down conductors spaced about 10 m apart. How many down conductors are needed?

  • (a) 3
  • (b) 4
  • (c) 6
  • (d) 10

Answer: (c) 6 — 60 m ÷ 10 m = 6 down conductors, spaced evenly around the perimeter.

Q3. A building has a perimeter of 80 m and needs Class III lightning protection, with down conductors spaced about 20 m apart. How many down conductors are needed?

  • (a) 2
  • (b) 4
  • (c) 8
  • (d) 16

Answer: (b) 4 — 80 m ÷ 20 m = 4 down conductors, because the wider spacing of the lower class needs fewer conductors.

Q4. Why should a down conductor follow the most direct route to the earth?

  • (a) To save copper
  • (b) To minimise inductance and the voltage rise along the conductor, and reduce the risk of side flashing
  • (c) To make it easier to paint
  • (d) To keep it out of sight

Answer: (b) To minimise inductance and the voltage rise along the conductor, and reduce the risk of side flashing — a longer, winding route raises the voltage on the conductor during a strike and invites sparks to nearby metal.

Q5. Why must sharp bends be avoided in a down conductor?

  • (a) They make the conductor hard to fix to the wall
  • (b) A sharp bend increases inductance and can cause a flashover across the bend
  • (c) They reduce the weight of the conductor
  • (d) They make testing impossible

Answer: (b) A sharp bend increases inductance and can cause a flashover across the bend — the fast-rising lightning current sees a sharp bend as a high impedance, so the voltage can arc across it.

Q6. What is a test joint (test clamp) on a down conductor?

  • (a) A joint that connects two air terminals
  • (b) A removable connection that lets the earth electrode be disconnected for resistance testing
  • (c) A joint that joins the down conductor to the roof
  • (d) A fuse that blows during a strike

Answer: (b) A removable connection that lets the earth electrode be disconnected for resistance testing — opening the test joint isolates the earth electrode so its resistance can be measured on its own.

Q7. Where is the test joint on a down conductor normally located?

  • (a) On the roof, next to the air terminal
  • (b) Near ground level, where it is accessible for testing
  • (c) Inside the main distribution board
  • (d) Underground, next to the electrode

Answer: (b) Near ground level, where it is accessible for testing — the joint must be easy to reach and open during periodic inspection and earth-resistance measurement.

Q8. Why are down conductors kept away from gas pipes and other services where possible?

  • (a) To keep the building tidy
  • (b) To prevent side flashing from the conductor to the service during a strike
  • (c) To stop the conductor from rusting
  • (d) To reduce the cost of the installation

Answer: (b) To prevent side flashing from the conductor to the service during a strike — the voltage on a down conductor rises sharply during a strike, so a nearby pipe can receive a dangerous spark unless separation or bonding is provided.

Q9. Which material is commonly used for down conductors?

  • (a) Copper or aluminium strip or round conductor
  • (b) PVC conduit
  • (c) Rubber cable
  • (d) Galvanised plastic

Answer: (a) Copper or aluminium strip or round conductor — both metals offer low resistance and survive weather, and a flat strip also has lower inductance than a round wire of the same area.

Q10. Why does a lightning protection system use several down conductors instead of just one?

  • (a) To make the building look symmetrical
  • (b) To share the lightning current, reduce the voltage rise, and provide a backup path if one is damaged
  • (c) To increase the earth resistance
  • (d) To attract more lightning

Answer: (b) To share the lightning current, reduce the voltage rise, and provide a backup path if one is damaged — parallel paths divide the tens of kiloamperes of a strike, so each conductor carries less current and the voltage on the system stays lower.