IEC Standards MCQs — Set 10

10 practice questions that apply IEC standards to real installation problems. Work each one out before checking the answer.

Q1. A single-phase load draws 24.2 A at 230 V. What is the smallest standard MCB rating above the load current?

  • (a) 20 A
  • (b) 25 A
  • (c) 32 A
  • (d) 40 A

Answer: (b) 25 A — standard MCB ratings run 6, 10, 16, 20, 25, 32, 40 A, so 25 A is the smallest rating above the 24.2 A load.

Q2. A 32 A type D MCB protects a transformer circuit. Between which currents does it trip magnetically?

  • (a) 96 A to 160 A
  • (b) 160 A to 320 A
  • (c) 320 A to 640 A
  • (d) 640 A to 1,280 A

Answer: (c) 320 A to 640 A — a type D MCB trips at 10× to 20× its rating, so 10 × 32 = 320 A and 20 × 32 = 640 A.

Q3. A 3 kW single-phase load runs at 230 V with a power factor of 0.9. What current does it draw?

  • (a) 13.0 A
  • (b) 14.5 A
  • (c) 11.8 A
  • (d) 16.7 A

Answer: (b) 14.5 A — I = P ÷ (V × pf) = 3,000 ÷ (230 × 0.9) = 3,000 ÷ 207 = 14.5 A.

Q4. A three-phase 9 kW load runs at 400 V with a power factor of 0.9. What line current does it draw?

  • (a) 14.4 A
  • (b) 17.0 A
  • (c) 22.5 A
  • (d) 12.9 A

Answer: (a) 14.4 A — I = P ÷ (√3 × V × pf) = 9,000 ÷ (1.732 × 400 × 0.9) = 9,000 ÷ 623.5 = 14.4 A.

Q5. During verification under IEC 60364-6, a 230 V circuit is insulation-tested at 500 V DC. What is the minimum acceptable insulation resistance?

  • (a) 0.25 MΩ
  • (b) 0.5 MΩ
  • (c) 1 MΩ
  • (d) 10 MΩ

Answer: (c) 1 MΩ — for circuits rated up to 500 V, IEC 60364-6 requires a minimum insulation resistance of 1 MΩ when tested at 500 V DC.

Q6. What does Class II equipment mean under IEC 61140 (protection against electric shock)?

  • (a) Equipment that must be earthed
  • (b) Equipment with double or reinforced insulation, needing no earth connection
  • (c) Equipment supplied only from SELV
  • (d) Equipment for use only outdoors

Answer: (b) Equipment with double or reinforced insulation, needing no earth connection — Class II equipment is marked with the double-square symbol and has no provision for earthing.

Q7. What does Class III equipment mean under IEC 61140?

  • (a) Equipment with double insulation
  • (b) Equipment that must be earthed through a 30 mA RCD
  • (c) Equipment supplied from a separated extra-low voltage (SELV) source, with no dangerous voltages inside
  • (d) Equipment rated above 1,000 V

Answer: (c) Equipment supplied from a separated extra-low voltage (SELV) source, with no dangerous voltages inside — Class III equipment is designed so that no voltage above extra-low voltage can appear in it.

Q8. Which IEC standard covers low-voltage switchgear and controlgear assemblies (distribution boards and panels)?

  • (a) IEC 60898
  • (b) IEC 60947-2
  • (c) IEC 61439
  • (d) IEC 60529

Answer: (c) IEC 61439 — this series covers low-voltage switchgear and controlgear assemblies, including the distribution boards and panels used in installations.

Q9. Which IEC standard covers the electrical equipment of machines?

  • (a) IEC 60204
  • (b) IEC 60364
  • (c) IEC 61000
  • (d) IEC 62305

Answer: (a) IEC 60204 — this series covers the electrical equipment of machines, including control panels, wiring and protection inside machinery.

Q10. Which IEC standard covers miniature circuit breakers (MCBs) for household use?

  • (a) IEC 60898
  • (b) IEC 60364
  • (c) IEC 60038
  • (d) IEC 62271

Answer: (a) IEC 60898 — it covers MCBs for household and similar installations; IEC 60364 covers the installations themselves.

Also read: Ohm’s Law Calculator | All MCQ Topics