IEC Standards MCQs — Set 8

10 practice questions on IEC voltage bands, supply tolerance and frequency. Work each one out before checking the answer.

Q1. According to the IEC, what is the upper limit of low voltage?

  • (a) 230 V AC
  • (b) 1,000 V AC / 1,500 V DC
  • (c) 11,000 V AC
  • (d) 400 V AC

Answer: (b) 1,000 V AC / 1,500 V DC — the IEC defines low voltage as up to 1,000 V AC or 1,500 V DC; above that is high voltage.

Q2. Which IEC standard defines standard voltages such as 230 V and 400 V?

  • (a) IEC 60364
  • (b) IEC 60529
  • (c) IEC 60038
  • (d) IEC 60898

Answer: (c) IEC 60038 — this standard lists the standard voltages for AC and DC supply systems, including 230 V single-phase and 400 V three-phase.

Q3. What is the standard single-phase supply voltage in most of the world under IEC 60038?

  • (a) 110 V
  • (b) 120 V
  • (c) 230 V
  • (d) 400 V

Answer: (c) 230 V — the IEC standard single-phase voltage is 230 V, with 400 V as the standard three-phase line voltage.

Q4. A 230 V supply is allowed a tolerance of ±10%. What is the permitted voltage range?

  • (a) 200 V to 260 V
  • (b) 207 V to 253 V
  • (c) 220 V to 240 V
  • (d) 210 V to 250 V

Answer: (b) 207 V to 253 V — 230 × 0.90 = 207 V and 230 × 1.10 = 253 V.

Q5. A 400 V three-phase supply is allowed a tolerance of ±10%. What is the permitted voltage range?

  • (a) 360 V to 440 V
  • (b) 380 V to 420 V
  • (c) 350 V to 450 V
  • (d) 390 V to 410 V

Answer: (a) 360 V to 440 V — 400 × 0.90 = 360 V and 400 × 1.10 = 440 V.

Q6. What is the standard supply frequency in most of the world?

  • (a) 25 Hz
  • (b) 50 Hz
  • (c) 60 Hz
  • (d) 400 Hz

Answer: (b) 50 Hz — most countries, including Europe, Asia, Africa and Australia, use a 50 Hz supply.

Q7. What supply frequency is used in North America?

  • (a) 25 Hz
  • (b) 50 Hz
  • (c) 60 Hz
  • (d) 100 Hz

Answer: (c) 60 Hz — North America uses 60 Hz, so equipment designed only for 50 Hz may not run correctly there.

Q8. Which IEC standard covers low-voltage electrical installations in buildings?

  • (a) IEC 60364
  • (b) IEC 60038
  • (c) IEC 60898
  • (d) IEC 61140

Answer: (a) IEC 60364 — it is the IEC standard for low-voltage electrical installations; IEC 60038 covers standard voltages and IEC 60898 covers MCBs for household use.

Q9. A 6 kW resistive heater runs at 230 V with a power factor of 1. What current does it draw?

  • (a) 26.1 A
  • (b) 24.2 A
  • (c) 30.0 A
  • (d) 13.0 A

Answer: (a) 26.1 A — I = P ÷ V = 6,000 ÷ 230 = 26.1 A, since a resistive load has a power factor of 1.

Q10. A three-phase 10 kW load runs at 400 V with a power factor of 0.85. What line current does it draw?

  • (a) 14.4 A
  • (b) 17.0 A
  • (c) 25.0 A
  • (d) 29.4 A

Answer: (b) 17.0 A — I = P ÷ (√3 × V × pf) = 10,000 ÷ (1.732 × 400 × 0.85) = 10,000 ÷ 588.9 = 17.0 A.