IEC Standards MCQs — Set 4

10 practice questions on IEC 60898 MCBs and the related RCD standards. Work each one out before checking the answer.

Q1. What does IEC 60898 cover?

  • (a) High-voltage circuit-breakers above 1 kV
  • (b) Circuit-breakers for overcurrent protection for household and similar installations (MCBs)
  • (c) Fuses for industrial motors
  • (d) Lightning surge protectors

Answer: (b) Circuit-breakers for overcurrent protection for household and similar installations (MCBs) — IEC 60898 is the MCB standard for homes, shops and similar premises.

Q2. What is the magnetic tripping range of a type B MCB?

  • (a) 1 to 2 times the rated current
  • (b) 3 to 5 times the rated current
  • (c) 5 to 10 times the rated current
  • (d) 10 to 20 times the rated current

Answer: (b) 3 to 5 times the rated current — a type B MCB trips magnetically (instantly) between 3× and 5× its rated current, so it suits resistive loads with little inrush.

Q3. What is the magnetic tripping range of a type C MCB?

  • (a) 3 to 5 times the rated current
  • (b) 5 to 10 times the rated current
  • (c) 10 to 20 times the rated current
  • (d) 20 to 30 times the rated current

Answer: (b) 5 to 10 times the rated current — a type C MCB tolerates moderate inrush, so it is the usual choice for general circuits with motors and discharge lamps.

Q4. What is the magnetic tripping range of a type D MCB?

  • (a) 3 to 5 times the rated current
  • (b) 5 to 10 times the rated current
  • (c) 10 to 20 times the rated current
  • (d) 20 to 50 times the rated current

Answer: (c) 10 to 20 times the rated current — a type D MCB tolerates very high inrush, so it is used for transformers, welders and motors with heavy starting currents.

Q5. A 16 A type B MCB is fitted on a lighting circuit. Between which currents does it trip magnetically?

  • (a) 16 A to 32 A
  • (b) 32 A to 48 A
  • (c) 48 A to 80 A
  • (d) 80 A to 160 A

Answer: (c) 48 A to 80 A — a type B MCB trips at 3× to 5× its rating, so 3 × 16 = 48 A and 5 × 16 = 80 A.

Q6. A 20 A type C MCB is fitted on a socket circuit. Between which currents does it trip magnetically?

  • (a) 60 A to 100 A
  • (b) 100 A to 200 A
  • (c) 200 A to 400 A
  • (d) 20 A to 40 A

Answer: (b) 100 A to 200 A — a type C MCB trips at 5× to 10× its rating, so 5 × 20 = 100 A and 10 × 20 = 200 A.

Q7. What is the highest rated current of an MCB covered by IEC 60898-1?

  • (a) 32 A
  • (b) 63 A
  • (c) 100 A
  • (d) 125 A

Answer: (d) 125 A — IEC 60898-1 covers MCBs with rated currents up to 125 A for household and similar installations.

Q8. An MCB is marked with a breaking capacity of 6 kA. The prospective fault current at its location is 8 kA. What should be done?

  • (a) Fit it anyway; 6 kA is enough for any fault
  • (b) Do not fit it; choose a breaker with a breaking capacity above 8 kA, such as 10 kA
  • (c) Fit two 6 kA MCBs in parallel
  • (d) Reduce the supply voltage

Answer: (b) Do not fit it; choose a breaker with a breaking capacity above 8 kA, such as 10 kA — a breaker must be able to interrupt the full prospective fault current at its point of installation.

Q9. Which IEC standard covers RCCBs — residual current devices without overcurrent protection?

  • (a) IEC 60898
  • (b) IEC 61008
  • (c) IEC 61009
  • (d) IEC 60269

Answer: (b) IEC 61008 — this standard covers RCCBs, which protect against earth leakage but need a separate MCB or fuse for overcurrent protection.

Q10. Which IEC standard covers RCBOs — residual current devices with overcurrent protection?

  • (a) IEC 60898
  • (b) IEC 61008
  • (c) IEC 61009
  • (d) IEC 60947-2

Answer: (c) IEC 61009 — this standard covers RCBOs, which combine RCD earth-leakage protection and MCB overcurrent protection in one device.