IEC Standards MCQs — Set 3

10 practice questions on IEC 60947, the standard for low-voltage switchgear and controlgear. Work each one out before checking the answer.

Q1. What does IEC 60947 cover?

  • (a) Household MCBs only
  • (b) Low-voltage switchgear and controlgear
  • (c) High-voltage transmission towers
  • (d) Domestic wiring accessories

Answer: (b) Low-voltage switchgear and controlgear — IEC 60947 covers circuit-breakers, switches, contactors, motor starters and control devices up to 1,000 V AC.

Q2. Which part of IEC 60947 covers circuit-breakers (MCCBs)?

  • (a) 60947-1
  • (b) 60947-2
  • (c) 60947-3
  • (d) 60947-4-1

Answer: (b) 60947-2 — this part covers low-voltage circuit-breakers, including moulded-case circuit-breakers (MCCBs) used in distribution boards.

Q3. Which part of IEC 60947 covers contactors and motor starters?

  • (a) 60947-2
  • (b) 60947-3
  • (c) 60947-4-1
  • (d) 60947-5-1

Answer: (c) 60947-4-1 — this part covers electromechanical contactors and motor starters, including overload relays for motor protection.

Q4. Which part of IEC 60947 covers switches, disconnectors and switch-disconnectors?

  • (a) 60947-1
  • (b) 60947-2
  • (c) 60947-3
  • (d) 60947-6

Answer: (c) 60947-3 — this part covers switches, disconnectors, switch-disconnectors and fuse-combination units used for isolation.

Q5. What does utilisation category AC-3 mean for a contactor?

  • (a) Switching resistive loads such as heaters
  • (b) Starting squirrel-cage motors and switching them off while running
  • (c) Switching control circuits only
  • (d) Switching DC loads

Answer: (b) Starting squirrel-cage motors and switching them off while running — AC-3 is the standard duty for motor contactors, which must handle the motor starting current.

Q6. What does utilisation category AC-1 mean?

  • (a) Squirrel-cage motor starting
  • (b) Non-inductive or slightly inductive loads, such as resistance furnaces
  • (c) Slip-ring motor starting
  • (d) DC motor switching

Answer: (b) Non-inductive or slightly inductive loads, such as resistance furnaces — AC-1 covers loads with a power factor of 0.95 or more, where the current is almost the same as the load current.

Q7. What is IEC 60947-1?

  • (a) The part for circuit-breakers
  • (b) The general rules that apply to all parts of the 60947 series
  • (c) The part for transfer switching equipment
  • (d) The part for terminal blocks

Answer: (b) The general rules that apply to all parts of the 60947 series — Part 1 defines the common terms, ratings, tests and marking rules used by the other parts.

Q8. Which part of IEC 60947 covers control circuit devices such as push-buttons and indicator lights?

  • (a) 60947-2
  • (b) 60947-4-1
  • (c) 60947-5-1
  • (d) 60947-7

Answer: (c) 60947-5-1 — this part covers control circuit devices and switching elements, including push-buttons, selector switches and pilot lights.

Q9. What is Icu for a circuit-breaker?

  • (a) The rated operating current
  • (b) The rated ultimate short-circuit breaking capacity
  • (c) The insulation voltage
  • (d) The tripping time in milliseconds

Answer: (b) The rated ultimate short-circuit breaking capacity — Icu is the highest fault current the breaker can interrupt safely, though it may not be fit for further service afterwards.

Q10. What is the difference between Ics and Icu?

  • (a) Ics is always larger than Icu
  • (b) After breaking its Ics, a breaker must still be usable; after breaking its Icu, it may need replacement
  • (c) Ics is the voltage rating and Icu is the current rating
  • (d) There is no difference; they are the same value

Answer: (b) After breaking its Ics, a breaker must still be usable; after breaking its Icu, it may need replacement — Ics is the service breaking capacity, expressed as a percentage of Icu, and the breaker must remain serviceable after an Ics fault.