IEC Standards MCQs — Set 3
10 practice questions on IEC 60947, the standard for low-voltage switchgear and controlgear. Work each one out before checking the answer.
Q1. What does IEC 60947 cover?
- (a) Household MCBs only
- (b) Low-voltage switchgear and controlgear
- (c) High-voltage transmission towers
- (d) Domestic wiring accessories
Answer: (b) Low-voltage switchgear and controlgear — IEC 60947 covers circuit-breakers, switches, contactors, motor starters and control devices up to 1,000 V AC.
Q2. Which part of IEC 60947 covers circuit-breakers (MCCBs)?
- (a) 60947-1
- (b) 60947-2
- (c) 60947-3
- (d) 60947-4-1
Answer: (b) 60947-2 — this part covers low-voltage circuit-breakers, including moulded-case circuit-breakers (MCCBs) used in distribution boards.
Q3. Which part of IEC 60947 covers contactors and motor starters?
- (a) 60947-2
- (b) 60947-3
- (c) 60947-4-1
- (d) 60947-5-1
Answer: (c) 60947-4-1 — this part covers electromechanical contactors and motor starters, including overload relays for motor protection.
Q4. Which part of IEC 60947 covers switches, disconnectors and switch-disconnectors?
- (a) 60947-1
- (b) 60947-2
- (c) 60947-3
- (d) 60947-6
Answer: (c) 60947-3 — this part covers switches, disconnectors, switch-disconnectors and fuse-combination units used for isolation.
Q5. What does utilisation category AC-3 mean for a contactor?
- (a) Switching resistive loads such as heaters
- (b) Starting squirrel-cage motors and switching them off while running
- (c) Switching control circuits only
- (d) Switching DC loads
Answer: (b) Starting squirrel-cage motors and switching them off while running — AC-3 is the standard duty for motor contactors, which must handle the motor starting current.
Q6. What does utilisation category AC-1 mean?
- (a) Squirrel-cage motor starting
- (b) Non-inductive or slightly inductive loads, such as resistance furnaces
- (c) Slip-ring motor starting
- (d) DC motor switching
Answer: (b) Non-inductive or slightly inductive loads, such as resistance furnaces — AC-1 covers loads with a power factor of 0.95 or more, where the current is almost the same as the load current.
Q7. What is IEC 60947-1?
- (a) The part for circuit-breakers
- (b) The general rules that apply to all parts of the 60947 series
- (c) The part for transfer switching equipment
- (d) The part for terminal blocks
Answer: (b) The general rules that apply to all parts of the 60947 series — Part 1 defines the common terms, ratings, tests and marking rules used by the other parts.
Q8. Which part of IEC 60947 covers control circuit devices such as push-buttons and indicator lights?
- (a) 60947-2
- (b) 60947-4-1
- (c) 60947-5-1
- (d) 60947-7
Answer: (c) 60947-5-1 — this part covers control circuit devices and switching elements, including push-buttons, selector switches and pilot lights.
Q9. What is Icu for a circuit-breaker?
- (a) The rated operating current
- (b) The rated ultimate short-circuit breaking capacity
- (c) The insulation voltage
- (d) The tripping time in milliseconds
Answer: (b) The rated ultimate short-circuit breaking capacity — Icu is the highest fault current the breaker can interrupt safely, though it may not be fit for further service afterwards.
Q10. What is the difference between Ics and Icu?
- (a) Ics is always larger than Icu
- (b) After breaking its Ics, a breaker must still be usable; after breaking its Icu, it may need replacement
- (c) Ics is the voltage rating and Icu is the current rating
- (d) There is no difference; they are the same value
Answer: (b) After breaking its Ics, a breaker must still be usable; after breaking its Icu, it may need replacement — Ics is the service breaking capacity, expressed as a percentage of Icu, and the breaker must remain serviceable after an Ics fault.
Also read: AFCI Breaker Keeps Tripping | All MCQ Topics