IEC Standards MCQs — Set 2
10 practice questions on IEC 60364, the standard for low-voltage electrical installations. Work each one out before checking the answer.
Q1. What does IEC 60364 cover?
- (a) High-voltage transmission lines above 132 kV
- (b) Low-voltage electrical installations up to 1,000 V AC
- (c) Only household appliances
- (d) Lightning protection of tall buildings
Answer: (b) Low-voltage electrical installations up to 1,000 V AC — IEC 60364 is the international standard for the design, erection and verification of low-voltage installations.
Q2. Which part of IEC 60364 covers protection against electric shock?
- (a) Part 1
- (b) Part 4-41
- (c) Part 5-52
- (d) Part 6
Answer: (b) Part 4-41 — IEC 60364-4-41 deals with protection against electric shock, including basic protection and fault protection.
Q3. IEC 60364-5-52 is mainly about which topic?
- (a) Verification and testing of installations
- (b) Protection against lightning
- (c) Selection and erection of wiring systems and current-carrying capacity of cables
- (d) Medical locations
Answer: (c) Selection and erection of wiring systems and current-carrying capacity of cables — Part 5-52 gives the cable sizing tables used to choose the right cable for a load.
Q4. Which part of IEC 60364 covers verification of an installation?
- (a) Part 4
- (b) Part 5
- (c) Part 6
- (d) Part 7
Answer: (c) Part 6 — IEC 60364-6 covers initial verification of a new installation and periodic inspection and testing of existing ones.
Q5. What does Part 7 of IEC 60364 deal with?
- (a) General definitions only
- (b) Requirements for special installations or locations, such as bathrooms and swimming pools
- (c) High-voltage switchgear ratings
- (d) EMC testing of equipment
Answer: (b) Requirements for special installations or locations, such as bathrooms and swimming pools — Part 7 adds extra rules where the risk is higher than in a normal room.
Q6. Which part of IEC 60364 covers earthing arrangements and protective conductors?
- (a) 60364-4-41
- (b) 60364-5-52
- (c) 60364-5-54
- (d) 60364-7-701
Answer: (c) 60364-5-54 — this part covers earthing arrangements, protective conductors and protective bonding conductors.
Q7. Under IEC 60364, what extra protection is required for general-purpose socket-outlets rated up to 32 A?
- (a) A 100 mA RCD
- (b) A 30 mA RCD
- (c) A 300 mA RCD
- (d) No RCD is required
Answer: (b) A 30 mA RCD — IEC 60364-4-41 requires additional protection by a 30 mA RCD for socket-outlets up to 32 A, because 30 mA is the level for personal protection.
Q8. Which IEC 60364 Part 7 section covers locations containing a bath or shower?
- (a) 60364-7-701
- (b) 60364-7-702
- (c) 60364-7-710
- (d) 60364-7-722
Answer: (a) 60364-7-701 — this section covers bathrooms and showers, where water makes the electric shock risk higher.
Q9. Which IEC 60364 Part 7 section covers medical locations?
- (a) 60364-7-701
- (b) 60364-7-705
- (c) 60364-7-710
- (d) 60364-7-714
Answer: (c) 60364-7-710 — this section covers medical locations such as hospitals, where patients may be especially vulnerable to electric shock.
Q10. Which IEC 60364 Part 7 section covers supplies for electric vehicles?
- (a) 60364-7-701
- (b) 60364-7-702
- (c) 60364-7-710
- (d) 60364-7-722
Answer: (d) 60364-7-722 — this section covers the supply of electric vehicles, including EV charging installations.