Harmonics MCQs — Set 8

10 practice questions on measuring harmonics — true-RMS meters, power quality analysers, what to measure and where to measure it.

Q1. Why must a true-RMS meter be used to measure current in a harmonic-rich circuit?

  • (a) An average-responding meter assumes a sine wave and under-reads distorted current
  • (b) A true-RMS meter only measures the fundamental
  • (c) Average meters always read higher than true RMS
  • (d) True-RMS meters cannot measure AC at all

Answer: (a) An average-responding meter assumes a sine wave and under-reads distorted current — true RMS measures the heating value of the actual waveform, including all harmonics.

Q2. Which instrument is best for a full harmonic survey of a plant?

  • (a) A simple neon tester
  • (b) A power quality analyser that records THD and the harmonic spectrum
  • (c) A megger insulation tester
  • (d) A continuity buzzer

Answer: (b) A power quality analyser that records THD and the harmonic spectrum — it measures voltage and current THD, individual harmonics and power factor over time.

Q3. A clamp meter that is NOT true-RMS reads 80 A on a circuit whose true-RMS current is 100 A. What does this show?

  • (a) The current waveform is distorted and the average-responding meter is under-reading
  • (b) The circuit is overloaded by 20 A
  • (c) The clamp meter is always correct
  • (d) The supply voltage has fallen by 20%

Answer: (a) The current waveform is distorted and the average-responding meter is under-reading — on a pure sine wave both meters agree, so a large gap points to harmonics.

Q4. What does a harmonic spectrum display show?

  • (a) The size of each harmonic order as a bar or line against its order or frequency
  • (b) Only the supply voltage
  • (c) The temperature of the transformer
  • (d) The resistance of the cable

Answer: (a) The size of each harmonic order as a bar or line against its order or frequency — the spectrum makes it easy to see which orders, such as the 5th or 7th, dominate.

Q5. What is the crest factor of a distorted current waveform with sharp peaks?

  • (a) Peak current ÷ RMS current, which is higher than the 1.414 of a pure sine wave
  • (b) RMS current ÷ peak current, which is always 1.414
  • (c) Average current ÷ peak current
  • (d) Fundamental current ÷ harmonic current

Answer: (a) Peak current ÷ RMS current, which is higher than the 1.414 of a pure sine wave — pulsed SMPS and rectifier currents have tall narrow peaks, so their crest factor is well above 1.414.

Q6. Where is harmonic distortion usually measured for compliance with a standard?

  • (a) At the point of common coupling (PCC), where the consumer connects to the supply
  • (b) Only inside the load itself
  • (c) At the far end of the earth wire
  • (d) Only at the generating station

Answer: (a) At the point of common coupling (PCC), where the consumer connects to the supply — limits such as IEEE 519 apply at the PCC, the boundary between supplier and consumer.

Q7. When checking for a triplen-harmonic problem, which conductor should be measured first?

  • (a) The neutral conductor, because triplen currents add there
  • (b) The earth wire only
  • (c) A single phase conductor only
  • (d) The lightning conductor

Answer: (a) The neutral conductor, because triplen currents add there — a high neutral current in a balanced system is a classic sign of triplen harmonics.

Q8. Each phase carries a 3rd-harmonic current of 12 A. What neutral current should a true-RMS clamp meter show from the 3rd harmonic?

  • (a) 0 A
  • (b) 12 A
  • (c) 24 A
  • (d) 36 A

Answer: (d) 36 A — triplen currents add in the neutral: 3 × 12 A = 36 A.

Q9. Why can an ordinary average-responding voltmeter give a misleading reading on a distorted supply?

  • (a) It is calibrated for a sine wave, so its reading is wrong when harmonics change the waveform shape
  • (b) It always reads the peak voltage correctly
  • (c) It measures only DC voltage
  • (d) It is unaffected by waveform shape

Answer: (a) It is calibrated for a sine wave, so its reading is wrong when harmonics change the waveform shape — the meter scales its average reading by the sine-wave factor 1.11, which no longer applies.

Q10. A power quality analyser shows a current THD of 35% at a motor control centre. What is the correct first conclusion?

  • (a) The current is heavily distorted and the harmonic sources should be identified
  • (b) The supply is a pure sine wave
  • (c) The THD reading can be ignored if the motor still runs
  • (d) The voltage THD must also be exactly 35%

Answer: (a) The current is heavily distorted and the harmonic sources should be identified — 35% current THD is high, so the dominant harmonic orders and their sources need investigation before choosing a fix.

Also read: Home Load Calculator | All MCQ Topics