Harmonics MCQs — Set 8
10 practice questions on measuring harmonics — true-RMS meters, power quality analysers, what to measure and where to measure it.
Q1. Why must a true-RMS meter be used to measure current in a harmonic-rich circuit?
- (a) An average-responding meter assumes a sine wave and under-reads distorted current
- (b) A true-RMS meter only measures the fundamental
- (c) Average meters always read higher than true RMS
- (d) True-RMS meters cannot measure AC at all
Answer: (a) An average-responding meter assumes a sine wave and under-reads distorted current — true RMS measures the heating value of the actual waveform, including all harmonics.
Q2. Which instrument is best for a full harmonic survey of a plant?
- (a) A simple neon tester
- (b) A power quality analyser that records THD and the harmonic spectrum
- (c) A megger insulation tester
- (d) A continuity buzzer
Answer: (b) A power quality analyser that records THD and the harmonic spectrum — it measures voltage and current THD, individual harmonics and power factor over time.
Q3. A clamp meter that is NOT true-RMS reads 80 A on a circuit whose true-RMS current is 100 A. What does this show?
- (a) The current waveform is distorted and the average-responding meter is under-reading
- (b) The circuit is overloaded by 20 A
- (c) The clamp meter is always correct
- (d) The supply voltage has fallen by 20%
Answer: (a) The current waveform is distorted and the average-responding meter is under-reading — on a pure sine wave both meters agree, so a large gap points to harmonics.
Q4. What does a harmonic spectrum display show?
- (a) The size of each harmonic order as a bar or line against its order or frequency
- (b) Only the supply voltage
- (c) The temperature of the transformer
- (d) The resistance of the cable
Answer: (a) The size of each harmonic order as a bar or line against its order or frequency — the spectrum makes it easy to see which orders, such as the 5th or 7th, dominate.
Q5. What is the crest factor of a distorted current waveform with sharp peaks?
- (a) Peak current ÷ RMS current, which is higher than the 1.414 of a pure sine wave
- (b) RMS current ÷ peak current, which is always 1.414
- (c) Average current ÷ peak current
- (d) Fundamental current ÷ harmonic current
Answer: (a) Peak current ÷ RMS current, which is higher than the 1.414 of a pure sine wave — pulsed SMPS and rectifier currents have tall narrow peaks, so their crest factor is well above 1.414.
Q6. Where is harmonic distortion usually measured for compliance with a standard?
- (a) At the point of common coupling (PCC), where the consumer connects to the supply
- (b) Only inside the load itself
- (c) At the far end of the earth wire
- (d) Only at the generating station
Answer: (a) At the point of common coupling (PCC), where the consumer connects to the supply — limits such as IEEE 519 apply at the PCC, the boundary between supplier and consumer.
Q7. When checking for a triplen-harmonic problem, which conductor should be measured first?
- (a) The neutral conductor, because triplen currents add there
- (b) The earth wire only
- (c) A single phase conductor only
- (d) The lightning conductor
Answer: (a) The neutral conductor, because triplen currents add there — a high neutral current in a balanced system is a classic sign of triplen harmonics.
Q8. Each phase carries a 3rd-harmonic current of 12 A. What neutral current should a true-RMS clamp meter show from the 3rd harmonic?
- (a) 0 A
- (b) 12 A
- (c) 24 A
- (d) 36 A
Answer: (d) 36 A — triplen currents add in the neutral: 3 × 12 A = 36 A.
Q9. Why can an ordinary average-responding voltmeter give a misleading reading on a distorted supply?
- (a) It is calibrated for a sine wave, so its reading is wrong when harmonics change the waveform shape
- (b) It always reads the peak voltage correctly
- (c) It measures only DC voltage
- (d) It is unaffected by waveform shape
Answer: (a) It is calibrated for a sine wave, so its reading is wrong when harmonics change the waveform shape — the meter scales its average reading by the sine-wave factor 1.11, which no longer applies.
Q10. A power quality analyser shows a current THD of 35% at a motor control centre. What is the correct first conclusion?
- (a) The current is heavily distorted and the harmonic sources should be identified
- (b) The supply is a pure sine wave
- (c) The THD reading can be ignored if the motor still runs
- (d) The voltage THD must also be exactly 35%
Answer: (a) The current is heavily distorted and the harmonic sources should be identified — 35% current THD is high, so the dominant harmonic orders and their sources need investigation before choosing a fix.