Harmonics MCQs — Set 7

10 practice questions on reducing harmonics — passive and active filters, line reactors, multi-pulse rectifiers and other mitigation methods.

Q1. What is a passive harmonic filter?

  • (a) A series inductor-capacitor circuit tuned to offer a low-impedance path at one harmonic frequency
  • (b) A device that injects an equal and opposite harmonic current
  • (c) A larger transformer with no filter components
  • (d) A circuit breaker that trips on harmonics

Answer: (a) A series inductor-capacitor circuit tuned to offer a low-impedance path at one harmonic frequency — the tuned LC branch shunts that harmonic away from the supply.

Q2. A passive filter is tuned to the 5th harmonic (250 Hz on a 50 Hz system). Which harmonic does it mainly remove?

  • (a) The 3rd harmonic
  • (b) The 5th harmonic
  • (c) The 7th harmonic
  • (d) The fundamental

Answer: (b) The 5th harmonic — a tuned filter has its lowest impedance at its tuned frequency, so it absorbs mainly that harmonic.

Q3. How does an active harmonic filter work?

  • (a) It measures the harmonic current and injects an equal current in the opposite phase to cancel it
  • (b) It disconnects the load whenever harmonics appear
  • (c) It adds a capacitor in series with the load
  • (d) It increases the supply voltage to swamp the harmonics

Answer: (a) It measures the harmonic current and injects an equal current in the opposite phase to cancel it — the injected current cancels the harmonic at the point of connection.

Q4. What is the main advantage of an active filter over a passive filter?

  • (a) It adapts automatically to changing loads and several harmonic orders at once
  • (b) It is always cheaper than a passive filter
  • (c) It needs no power supply of its own
  • (d) It can only filter one fixed harmonic

Answer: (a) It adapts automatically to changing loads and several harmonic orders at once — a passive filter is fixed to one tuned frequency, while an active filter tracks the load.

Q5. What does a line reactor (AC choke) do when fitted in front of a VFD?

  • (a) It smooths the pulsed input current and reduces harmonic distortion
  • (b) It increases the harmonic current drawn by the drive
  • (c) It converts the drive output to DC
  • (d) It replaces the drive’s rectifier

Answer: (a) It smooths the pulsed input current and reduces harmonic distortion — the added inductance slows the current pulses, lowering the harmonic content.

Q6. Compared with a 6-pulse rectifier, what is the main harmonic benefit of a 12-pulse rectifier?

  • (a) It eliminates the 5th and 7th harmonics, leaving mainly the 11th and 13th
  • (b) It produces larger 5th and 7th harmonics
  • (c) It produces only triplen harmonics
  • (d) It has no effect on harmonics at all

Answer: (a) It eliminates the 5th and 7th harmonics, leaving mainly the 11th and 13th — a 12-pulse rectifier generates harmonics of order 12k ± 1, so the lowest are the 11th and 13th, which are smaller.

Q7. What does a phase-shifting transformer do in harmonic mitigation?

  • (a) It shifts the phase of one rectifier so its 5th and 7th harmonics cancel those of another
  • (b) It steps the voltage up to remove harmonics
  • (c) It stores harmonic energy in its core
  • (d) It converts single-phase to three-phase

Answer: (a) It shifts the phase of one rectifier so its 5th and 7th harmonics cancel those of another — two rectifiers fed 30° apart cancel each other’s 5th and 7th harmonics, forming a 12-pulse system.

Q8. Why is a detuned reactor fitted in series with a power-factor correction capacitor?

  • (a) To shift the resonance frequency away from a harmonic so the capacitor does not amplify it
  • (b) To increase the capacitance of the bank
  • (c) To make the capacitor absorb more harmonic current
  • (d) To raise the supply voltage

Answer: (a) To shift the resonance frequency away from a harmonic so the capacitor does not amplify it — the reactor moves the series resonance below the lowest harmful harmonic, usually the 5th.

Q9. In a building with heavy single-phase electronic loads, what neutral sizing is commonly recommended?

  • (a) A neutral rated at 200% of the phase conductor, to carry the added triplen current
  • (b) A neutral half the size of the phase conductor
  • (c) No neutral at all
  • (d) A neutral the same size as the earth wire only

Answer: (a) A neutral rated at 200% of the phase conductor, to carry the added triplen current — triplen currents add in the neutral, so it can carry more current than a phase conductor.

Q10. How does a delta-wye transformer help reduce triplen harmonics on the supply side?

  • (a) The delta winding traps triplen currents so they do not flow back into the supply
  • (b) It converts triplen harmonics into the fundamental
  • (c) It doubles the triplen current on the supply
  • (d) It only works on the 5th harmonic

Answer: (a) The delta winding traps triplen currents so they do not flow back into the supply — triplen currents circulate in the closed delta and are blocked from the primary side.

Also read: GFCI Outlet Keeps Tripping | All MCQ Topics