Q1. What effect do 5th and 7th harmonics have on a three-phase induction motor?

  • (a) They produce torque pulsations and vibration
  • (b) They make the motor run silently at higher efficiency
  • (c) They reduce the motor current to zero
  • (d) They increase the synchronous speed

Answer: (a) They produce torque pulsations and vibration — the 5th (negative sequence) and 7th (positive sequence) harmonics set up fields at different speeds, so torque ripples instead of staying smooth.

Q2. Why does the 5th harmonic create a braking effect in a motor?

  • (a) It is a negative-sequence harmonic, so its field rotates opposite to the rotor
  • (b) It is a triplen harmonic that flows in the neutral
  • (c) It raises the supply frequency to 250 Hz
  • (d) It short-circuits the stator winding

Answer: (a) It is a negative-sequence harmonic, so its field rotates opposite to the rotor — the counter-rotating field opposes the motor, wasting energy as heat.

Q3. Why are power-factor correction capacitors at risk in a harmonic-rich system?

  • (a) A capacitor’s impedance falls as frequency rises, so it absorbs large harmonic currents
  • (b) A capacitor’s impedance rises as frequency rises, so it blocks harmonics
  • (c) Capacitors only conduct the fundamental current
  • (d) Capacitors are unaffected by frequency

Answer: (a) A capacitor’s impedance falls as frequency rises, so it absorbs large harmonic currents — at the 5th harmonic the capacitive reactance is one-fifth of its 50 Hz value, so harmonic current flows easily into the bank.

Q4. In a balanced three-phase system with heavy triplen harmonics, why can the neutral conductor overheat even though the phases are balanced?

  • (a) Triplen harmonics add in the neutral, so neutral current can exceed phase current
  • (b) The neutral carries no current in a balanced system
  • (c) The phases cancel the neutral current completely
  • (d) Triplen harmonics flow only in the earth wire

Answer: (a) Triplen harmonics add in the neutral, so neutral current can exceed phase current — the three in-phase triplen currents sum, and the neutral was often sized only for imbalance.

Q5. How does the skin effect worsen cable heating under harmonics?

  • (a) At higher harmonic frequencies current crowds to the conductor surface, raising effective resistance
  • (b) Skin effect only occurs at 50 Hz, never at harmonic frequencies
  • (c) Skin effect cools the conductor
  • (d) Skin effect reduces the cable resistance

Answer: (a) At higher harmonic frequencies current crowds to the conductor surface, raising effective resistance — the higher resistance at harmonic frequencies increases I²R heating in the cable.

Q6. A motor supplied with distorted voltage runs hotter than normal at the same mechanical load. What is the main cause?

  • (a) Harmonic currents cause extra copper and iron losses in the motor
  • (b) The motor is drawing less current than normal
  • (c) The supply voltage is a pure sine wave
  • (d) The motor bearings are over-greased

Answer: (a) Harmonic currents cause extra copper and iron losses in the motor — harmonics add losses that do no useful work, so the motor heats up.

Q7. What is the frequency of the 7th harmonic on a 60 Hz supply?

  • (a) 350 Hz
  • (b) 420 Hz
  • (c) 300 Hz
  • (d) 120 Hz

Answer: (b) 420 Hz — the 7th harmonic is 7 × the fundamental, so 7 × 60 = 420 Hz.

Q8. A capacitor bank keeps blowing fuses in a plant with many VFDs. What is the most likely cause?

  • (a) Harmonic currents overloading the capacitors, possibly with resonance
  • (b) The capacitors being too large for the load
  • (c) The supply being free of harmonics
  • (d) The fuses being rated too high

Answer: (a) Harmonic currents overloading the capacitors, possibly with resonance — harmonic current flows readily into the low-impedance capacitors, and resonance can amplify it until fuses blow.

Q9. Each phase carries a 3rd-harmonic current of 8 A. What is the neutral current from the 3rd harmonic?

  • (a) 8 A
  • (b) 16 A
  • (c) 24 A
  • (d) 32 A

Answer: (c) 24 A — triplen currents add in the neutral: 3 × 8 A = 24 A.

Q10. Harmonic voltage distortion can stress motor insulation because:

  • (a) Distorted waveforms have higher peak voltages and steep voltage steps
  • (b) Harmonics always lower the peak voltage
  • (c) Insulation is only stressed by the fundamental
  • (d) Harmonic voltage cannot reach the motor terminals

Answer: (a) Distorted waveforms have higher peak voltages and steep voltage steps — the sharp peaks and fast-rising edges stress the winding insulation more than a smooth sine wave.