Harmonics MCQs — Set 5

10 practice questions on how harmonics affect transformers — extra losses, overheating, derating and the K-rated transformers built to handle them.

Q1. In a transformer, which loss increases most sharply with harmonic currents?

  • (a) Hysteresis loss only
  • (b) Eddy-current loss, which rises with the square of the frequency
  • (c) Dielectric loss in the oil
  • (d) Core loss, which falls as frequency rises

Answer: (b) Eddy-current loss, which rises with the square of the frequency — a harmonic at n times the fundamental produces roughly n² times the eddy-current loss of the same current at fundamental frequency.

Q2. What does the K-factor of a transformer indicate?

  • (a) Its voltage ratio
  • (b) Its ability to handle harmonic currents without overheating
  • (c) Its short-circuit impedance only
  • (d) Its oil temperature at full load

Answer: (b) Its ability to handle harmonic currents without overheating — a higher K-factor means the transformer is designed for a heavier harmonic load.

Q3. A transformer supplies a heavily harmonic load and runs hot even though its RMS load current is below its rating. What is the most likely cause?

  • (a) Harmonic currents causing extra eddy-current and copper losses
  • (b) The transformer oil being too clean
  • (c) The supply voltage being too pure
  • (d) The load being purely resistive

Answer: (a) Harmonic currents causing extra eddy-current and copper losses — harmonics add losses that the nameplate rating (based on sine-wave current) does not cover.

Q4. Which transformer is the correct choice for a building full of computers and VFDs?

  • (a) A standard distribution transformer with no harmonic rating
  • (b) A K-rated transformer, such as K-13
  • (c) An autotransformer with no neutral
  • (d) A transformer rated only for the fundamental current

Answer: (b) A K-rated transformer, such as K-13 — K-rated transformers have heavier windings and cores designed to carry harmonic currents without overheating.

Q5. What is derating a transformer for harmonic loads?

  • (a) Running it above its nameplate rating
  • (b) Reducing its allowed load below its nameplate rating so harmonic losses do not overheat it
  • (c) Changing its voltage ratio
  • (d) Removing its cooling fans

Answer: (b) Reducing its allowed load below its nameplate rating so harmonic losses do not overheat it — derating leaves headroom for the extra harmonic heating.

Q6. How does a delta-connected winding help with triplen harmonics?

  • (a) Triplen currents circulate inside the delta instead of flowing out onto the supply
  • (b) The delta winding converts triplen harmonics to DC
  • (c) The delta winding doubles the triplen current
  • (d) The delta winding removes the fundamental as well

Answer: (a) Triplen currents circulate inside the delta instead of flowing out onto the supply — triplen harmonics are zero-sequence, so they are trapped in the closed delta loop.

Q7. A transformer feeding non-linear loads hums loudly and vibrates more than usual. What is the likely reason?

  • (a) Harmonic currents causing extra magnetostriction and vibration in the core
  • (b) The transformer being underloaded
  • (c) The supply frequency being exactly 50 Hz
  • (d) The load drawing pure sine-wave current

Answer: (a) Harmonic currents causing extra magnetostriction and vibration in the core — harmonic flux components make the core vibrate at harmonic frequencies, increasing audible noise.

Q8. Harmonic currents increase the copper (I²R) loss in a transformer winding because:

  • (a) The total RMS current is higher than the fundamental current alone
  • (b) The winding resistance falls at harmonic frequencies
  • (c) Harmonics reduce the current in the winding
  • (d) Copper loss depends only on voltage, not current

Answer: (a) The total RMS current is higher than the fundamental current alone — RMS current includes every harmonic, so I²R loss rises even when the useful fundamental power is unchanged.

Q9. Which K-factor rating is suitable for a heavier harmonic load — K-4 or K-13?

  • (a) K-4, because a lower number means heavier duty
  • (b) K-13, because a higher K-factor means it can handle more harmonic heating
  • (c) Both are identical in every case
  • (d) Neither; K-factor applies only to motors

Answer: (b) K-13, because a higher K-factor means it can handle more harmonic heating — K-13 is designed for loads with a high harmonic content, while K-4 suits only light harmonic loads.

Q10. What is the main risk if a standard transformer is loaded with a high-harmonic load at full nameplate current?

  • (a) It will run cooler than normal
  • (b) Hot spots, insulation ageing and a shorter life
  • (c) Its voltage ratio will double
  • (d) Its frequency will change to 60 Hz

Answer: (b) Hot spots, insulation ageing and a shorter life — the extra harmonic losses create local overheating that ages the insulation faster.