Fuse MCQs — Set 8
10 practice questions on fuse discrimination (selectivity) — making sure only the fuse nearest the fault operates — with answers and explanations.
Q1. Discrimination (selectivity) between fuses means…
- (a) only the fuse nearest the fault operates
- (b) all fuses blow together
- (c) the largest fuse always blows first
- (d) fuses are replaced in pairs
Answer: (a) only the fuse nearest the fault operates — the faulty circuit is isolated while healthy circuits stay in supply.
Q2. For good discrimination, the upstream fuse rating should be…
- (a) lower than the downstream fuse
- (b) higher than the downstream fuse
- (c) equal to the downstream fuse
- (d) half the downstream fuse
Answer: (b) higher than the downstream fuse — the downstream fuse must melt first, so the upstream fuse needs the larger rating.
Q3. Which curves are compared to check discrimination between two fuses?
- (a) Voltage-current curves
- (b) Time-current curves
- (c) Power-factor curves
- (d) Load-duration curves
Answer: (b) Time-current curves — if the downstream fuse curve lies below the upstream curve at the fault current, discrimination is achieved.
Q4. A common rule of thumb for discrimination is that the upstream fuse rating should be at least…
- (a) equal to the downstream rating
- (b) twice the downstream rating
- (c) ten times the downstream rating
- (d) half the downstream rating
Answer: (b) twice the downstream rating — a 2:1 ratio between upstream and downstream ratings usually gives good discrimination.
Q5. If discrimination fails, what happens?
- (a) Only the faulty circuit is isolated
- (b) Healthy circuits also lose supply
- (c) The fault current falls
- (d) The fuse rating increases
Answer: (b) Healthy circuits also lose supply — the upstream fuse blows as well, cutting off circuits that have no fault.
Q6. Discrimination between protective devices is also called…
- (a) selectivity
- (b) grading
- (c) earthing
- (d) bonding
Answer: (a) selectivity — discrimination and selectivity mean the same thing: only the device nearest the fault operates.
Q7. A downstream fuse is rated 10 A. Using the 2:1 rule, the upstream fuse should be at least…
- (a) 5 A
- (b) 10 A
- (c) 20 A
- (d) 40 A
Answer: (c) 20 A — 2 × 10 A = 20 A is the minimum upstream rating for discrimination.
Q8. A downstream fuse is rated 16 A. Using the 2:1 rule, the upstream fuse should be at least…
- (a) 8 A
- (b) 16 A
- (c) 24 A
- (d) 32 A
Answer: (d) 32 A — 2 × 16 A = 32 A is the minimum upstream rating for discrimination.
Q9. A downstream fuse is rated 32 A. Which upstream rating gives good discrimination?
- (a) 32 A
- (b) 40 A
- (c) 63 A
- (d) 16 A
Answer: (c) 63 A — the 2:1 rule needs about 64 A (2 × 32 A), and 63 A is the nearest standard rating.
Q10. Time grading in discrimination means…
- (a) the upstream device is deliberately slower so the downstream device clears the fault first
- (b) both devices operate at the same time
- (c) the upstream device is faster
- (d) time is not considered
Answer: (a) the upstream device is deliberately slower so the downstream device clears the fault first — grading the operating times keeps the healthy circuits in supply.
Also read: Electrical Safety MCQs | All MCQ Topics