Fuse MCQs — Set 6
10 practice questions on the fusing factor — calculating minimum fusing current and rated current — with worked answers.
Q1. Fusing factor is defined as…
- (a) rated current ÷ minimum fusing current
- (b) minimum fusing current ÷ rated current
- (c) breaking capacity ÷ rated current
- (d) rated voltage ÷ rated current
Answer: (b) minimum fusing current ÷ rated current — fusing factor = minimum fusing current / rated current, and it is always greater than 1.
Q2. A fuse rated 40 A has a minimum fusing current of 60 A. What is its fusing factor?
- (a) 1.2
- (b) 1.5
- (c) 2.0
- (d) 0.67
Answer: (b) 1.5 — fusing factor = 60 ÷ 40 = 1.5.
Q3. A 30 A fuse has a fusing factor of 1.5. What is its minimum fusing current?
- (a) 20 A
- (b) 45 A
- (c) 30 A
- (d) 60 A
Answer: (b) 45 A — minimum fusing current = 1.5 × 30 = 45 A.
Q4. A fuse rated 50 A melts at a minimum current of 80 A. What is its fusing factor?
- (a) 1.5
- (b) 1.6
- (c) 1.4
- (d) 2.0
Answer: (b) 1.6 — fusing factor = 80 ÷ 50 = 1.6.
Q5. A fuse has a minimum fusing current of 90 A and a fusing factor of 1.5. What is its rated current?
- (a) 45 A
- (b) 135 A
- (c) 60 A
- (d) 30 A
Answer: (c) 60 A — rated current = 90 ÷ 1.5 = 60 A.
Q6. A fuse rated 80 A has a minimum fusing current of 120 A. What is its fusing factor?
- (a) 1.2
- (b) 1.5
- (c) 1.8
- (d) 2.0
Answer: (b) 1.5 — fusing factor = 120 ÷ 80 = 1.5.
Q7. A fuse rated 50 A has a minimum fusing current of 100 A. What is its fusing factor?
- (a) 1.5
- (b) 1.6
- (c) 2.0
- (d) 2.5
Answer: (c) 2.0 — fusing factor = 100 ÷ 50 = 2.0.
Q8. A fuse has a fusing factor of 2.0 and a rated current of 35 A. What is its minimum fusing current?
- (a) 17.5 A
- (b) 35 A
- (c) 70 A
- (d) 105 A
Answer: (c) 70 A — minimum fusing current = 2.0 × 35 = 70 A.
Q9. “Breaking capacity” of a fuse means…
- (a) the current it carries continuously
- (b) the maximum fault current it can safely interrupt without damage
- (c) the current at which it starts to melt
- (d) the voltage it can withstand
Answer: (b) the maximum fault current it can safely interrupt without damage — beyond this current the fuse may explode or fail to clear the fault.
Q10. A fuse has a minimum fusing current of 150 A and a fusing factor of 1.5. What is its rated current?
- (a) 75 A
- (b) 100 A
- (c) 225 A
- (d) 50 A
Answer: (b) 100 A — rated current = 150 ÷ 1.5 = 100 A.
Also read: Breaker and Protection MCQs | All MCQ Topics