Fire Alarm MCQs — Set 10
10 practice questions on fire alarm system design — choosing the right system for each building and sizing its power — with answers and explanations.
Q1. A large multi-storey school needs to know exactly which classroom a detector operated in. Which system suits it best?
- (a) A conventional system
- (b) An addressable system
- (c) A system with sounders only
- (d) A system with no panel
Answer: (b) An addressable system — it identifies the exact device, so staff know precisely which classroom to check.
Q2. What type of detector covers a large open space, such as a warehouse, with a single device?
- (a) A point smoke detector
- (b) A beam detector, which sends a light beam across the space
- (c) A manual call point
- (d) A fixed-temperature heat detector
Answer: (b) A beam detector, which sends a light beam across the space — smoke crossing the beam reduces the received light and triggers the alarm.
Q3. A data centre needs the earliest possible warning of a fire. Which detection method is best?
- (a) A fixed-temperature heat detector
- (b) An aspirating smoke detection system that samples the air continuously
- (c) A flame detector
- (d) A manual call point
Answer: (b) An aspirating smoke detection system that samples the air continuously — it detects tiny amounts of smoke long before a point detector would.
Q4. Which detector is the right choice for a commercial kitchen?
- (a) An optical smoke detector
- (b) A heat detector
- (c) An ionisation smoke detector
- (d) A beam detector
Answer: (b) A heat detector — cooking smoke and steam would false-alarm a smoke detector, while a heat detector responds only to temperature.
Q5. Six sounders each draw 0.05 A from a 24 V DC supply. What is the total current and total power of the six sounders?
- (a) 0.3 A and 7.2 W
- (b) 0.05 A and 1.2 W
- (c) 0.6 A and 14.4 W
- (d) 3 A and 72 W
Answer: (a) 0.3 A and 7.2 W — total current = 6 × 0.05 = 0.3 A, and power = 24 × 0.3 = 7.2 W.
Q6. A panel draws 0.4 A in standby and 1.5 A in alarm. What battery charge is needed for 24 hours standby plus 30 minutes (0.5 h) in alarm?
- (a) 9.6 Ah
- (b) 10.35 Ah
- (c) 12 Ah
- (d) 20 Ah
Answer: (b) 10.35 Ah — standby = 0.4 × 24 = 9.6 Ah, alarm = 1.5 × 0.5 = 0.75 Ah, total = 9.6 + 0.75 = 10.35 Ah.
Q7. A small shop has one open sales area and a store room. Which system is the most sensible choice?
- (a) A large addressable system with many loops
- (b) A simple conventional system with a zone for each area
- (c) No system at all
- (d) An aspirating system
Answer: (b) A simple conventional system with a zone for each area — the areas are small enough to search quickly and the cost stays low.
Q8. When the fire alarm sounds, what should occupants do?
- (a) Finish their work first, then leave
- (b) Leave at once by the nearest safe escape route and go to the assembly point
- (c) Use the lift to reach the ground floor quickly
- (d) Open all the windows
Answer: (b) Leave at once by the nearest safe escape route and go to the assembly point — lifts must not be used in a fire.
Q9. In a hotel, why are sounders fitted in bedrooms as well as corridors?
- (a) Because corridors are too quiet
- (b) Because sleeping guests behind a closed door may not hear a corridor sounder well enough to wake
- (c) Because bedrooms have more detectors
- (d) Because the panel needs more circuits
Answer: (b) Because sleeping guests behind a closed door may not hear a corridor sounder well enough to wake — bedroom sounders deliver the required level at the bedhead.
Q10. A fire alarm system is being designed for a building with high ceilings and large open halls. Which combination is most suitable?
- (a) Point smoke detectors only, spaced widely apart
- (b) Beam detectors or aspirating detection, with an addressable panel to pinpoint the location
- (c) Manual call points only
- (d) Heat detectors only
Answer: (b) Beam detectors or aspirating detection, with an addressable panel to pinpoint the location — point detectors under a very high ceiling respond late, while beams and aspirating systems cover large open volumes.
Also read: GFCI Outlet Keeps Tripping | All MCQ Topics