Fire Alarm MCQs — Set 10

10 practice questions on fire alarm system design — choosing the right system for each building and sizing its power — with answers and explanations.

Q1. A large multi-storey school needs to know exactly which classroom a detector operated in. Which system suits it best?

  • (a) A conventional system
  • (b) An addressable system
  • (c) A system with sounders only
  • (d) A system with no panel

Answer: (b) An addressable system — it identifies the exact device, so staff know precisely which classroom to check.

Q2. What type of detector covers a large open space, such as a warehouse, with a single device?

  • (a) A point smoke detector
  • (b) A beam detector, which sends a light beam across the space
  • (c) A manual call point
  • (d) A fixed-temperature heat detector

Answer: (b) A beam detector, which sends a light beam across the space — smoke crossing the beam reduces the received light and triggers the alarm.

Q3. A data centre needs the earliest possible warning of a fire. Which detection method is best?

  • (a) A fixed-temperature heat detector
  • (b) An aspirating smoke detection system that samples the air continuously
  • (c) A flame detector
  • (d) A manual call point

Answer: (b) An aspirating smoke detection system that samples the air continuously — it detects tiny amounts of smoke long before a point detector would.

Q4. Which detector is the right choice for a commercial kitchen?

  • (a) An optical smoke detector
  • (b) A heat detector
  • (c) An ionisation smoke detector
  • (d) A beam detector

Answer: (b) A heat detector — cooking smoke and steam would false-alarm a smoke detector, while a heat detector responds only to temperature.

Q5. Six sounders each draw 0.05 A from a 24 V DC supply. What is the total current and total power of the six sounders?

  • (a) 0.3 A and 7.2 W
  • (b) 0.05 A and 1.2 W
  • (c) 0.6 A and 14.4 W
  • (d) 3 A and 72 W

Answer: (a) 0.3 A and 7.2 W — total current = 6 × 0.05 = 0.3 A, and power = 24 × 0.3 = 7.2 W.

Q6. A panel draws 0.4 A in standby and 1.5 A in alarm. What battery charge is needed for 24 hours standby plus 30 minutes (0.5 h) in alarm?

  • (a) 9.6 Ah
  • (b) 10.35 Ah
  • (c) 12 Ah
  • (d) 20 Ah

Answer: (b) 10.35 Ah — standby = 0.4 × 24 = 9.6 Ah, alarm = 1.5 × 0.5 = 0.75 Ah, total = 9.6 + 0.75 = 10.35 Ah.

Q7. A small shop has one open sales area and a store room. Which system is the most sensible choice?

  • (a) A large addressable system with many loops
  • (b) A simple conventional system with a zone for each area
  • (c) No system at all
  • (d) An aspirating system

Answer: (b) A simple conventional system with a zone for each area — the areas are small enough to search quickly and the cost stays low.

Q8. When the fire alarm sounds, what should occupants do?

  • (a) Finish their work first, then leave
  • (b) Leave at once by the nearest safe escape route and go to the assembly point
  • (c) Use the lift to reach the ground floor quickly
  • (d) Open all the windows

Answer: (b) Leave at once by the nearest safe escape route and go to the assembly point — lifts must not be used in a fire.

Q9. In a hotel, why are sounders fitted in bedrooms as well as corridors?

  • (a) Because corridors are too quiet
  • (b) Because sleeping guests behind a closed door may not hear a corridor sounder well enough to wake
  • (c) Because bedrooms have more detectors
  • (d) Because the panel needs more circuits

Answer: (b) Because sleeping guests behind a closed door may not hear a corridor sounder well enough to wake — bedroom sounders deliver the required level at the bedhead.

Q10. A fire alarm system is being designed for a building with high ceilings and large open halls. Which combination is most suitable?

  • (a) Point smoke detectors only, spaced widely apart
  • (b) Beam detectors or aspirating detection, with an addressable panel to pinpoint the location
  • (c) Manual call points only
  • (d) Heat detectors only

Answer: (b) Beam detectors or aspirating detection, with an addressable panel to pinpoint the location — point detectors under a very high ceiling respond late, while beams and aspirating systems cover large open volumes.