Fire Alarm MCQs — Set 6
10 practice questions on fire alarm power supplies and battery backup — standby time, alarm time and load calculations — with answers and explanations.
Q1. What two power sources does a fire alarm panel normally have?
- (a) Mains supply and a standby battery
- (b) Two mains supplies
- (c) A battery and a generator only
- (d) Solar panels and a battery
Answer: (a) Mains supply and a standby battery — the battery takes over automatically if the mains fails.
Q2. What supply voltage do fire alarm panels commonly run on?
- (a) 12 V AC
- (b) 24 V DC
- (c) 110 V AC
- (d) 230 V DC
Answer: (b) 24 V DC — 24 V DC is the common operating voltage for fire alarm panels and their devices.
Q3. How long is the standby battery commonly specified to support the system in standby (no alarm)?
- (a) 1 hour
- (b) 6 hours
- (c) 24 hours
- (d) 72 hours
Answer: (c) 24 hours — a common specification is 24 hours standby followed by alarm operation.
Q4. After 24 hours of standby, how long is the battery commonly specified to power the system in alarm?
- (a) 5 minutes
- (b) 15 minutes
- (c) 30 minutes
- (d) 2 hours
Answer: (c) 30 minutes — the common specification is 24 hours standby plus 30 minutes in alarm.
Q5. A fire alarm sounder runs on 24 V DC and draws 0.05 A. What power does it consume? (P = V × I)
- (a) 0.5 W
- (b) 1.2 W
- (c) 2.4 W
- (d) 12 W
Answer: (b) 1.2 W — P = V × I = 24 × 0.05 = 1.2 W.
Q6. Four sounders each draw 0.1 A from a 24 V DC supply. What is the total power of the four sounders?
- (a) 2.4 W
- (b) 4.8 W
- (c) 9.6 W
- (d) 24 W
Answer: (c) 9.6 W — each sounder takes 24 × 0.1 = 2.4 W, and 4 × 2.4 = 9.6 W.
Q7. A panel draws 0.25 A in standby. How much charge does it use from the battery in 24 hours of standby?
- (a) 3 Ah
- (b) 6 Ah
- (c) 12 Ah
- (d) 24 Ah
Answer: (b) 6 Ah — charge = current × time = 0.25 × 24 = 6 Ah.
Q8. What happens when the mains supply to a fire alarm panel fails?
- (a) The system switches off completely
- (b) The panel switches over to the standby battery automatically
- (c) The sounders operate continuously until the mains returns
- (d) The detectors stop working but the panel stays on
Answer: (b) The panel switches over to the standby battery automatically — there is no break in protection.
Q9. What is the job of the battery charger inside a fire alarm panel?
- (a) To sound the alarm
- (b) To keep the standby battery fully charged from the mains supply
- (c) To test the detectors
- (d) To cool the panel
Answer: (b) To keep the standby battery fully charged from the mains supply — the battery must be ready the moment the mains fails.
Q10. Why does the panel show a fault if the standby battery voltage is low?
- (a) Because a low battery cannot support the system through a mains failure
- (b) Because the sounders would be too loud
- (c) Because the detectors would detect too much smoke
- (d) Because the mains supply would trip
Answer: (a) Because a low battery cannot support the system through a mains failure — a weak battery means the backup is not reliable, so it must be reported.