Energy Meter MCQs — Set 5
Single-phase vs three-phase meters, CT-operated metering and the multiplying factor — with worked calculations.
Q1. A three-phase, 4-wire energy meter has how many measuring elements?
- (a) One element
- (b) Two elements
- (c) Three elements
- (d) Four elements
Answer: (c) Three elements — a 4-wire system needs one current coil and one pressure coil per phase, so three elements in total.
Q2. A CT-operated meter uses a current transformer with ratio 100/5 A. If the meter records 2 kWh, what is the actual energy consumed?
- (a) 2 kWh
- (b) 10 kWh
- (c) 40 kWh
- (d) 100 kWh
Answer: (c) 40 kWh — multiplying factor = 100 ÷ 5 = 20, so actual energy = 2 × 20 = 40 kWh.
Q3. A meter with a CT ratio of 200/5 A records 5 kWh. What is the actual consumption?
- (a) 25 kWh
- (b) 200 kWh
- (c) 40 kWh
- (d) 1,000 kWh
Answer: (b) 200 kWh — multiplying factor = 200 ÷ 5 = 40, so actual energy = 5 × 40 = 200 kWh.
Q4. A 2-element energy meter is used for which supply?
- (a) Single-phase, 2-wire
- (b) Three-phase, 3-wire
- (c) Three-phase, 4-wire
- (d) DC supply
Answer: (b) Three-phase, 3-wire — by Blondel’s theorem, a 3-wire system needs only two elements (two wattmeters) to measure total power.
Q5. An HT meter has a CT ratio of 100/5 A and a PT ratio of 11,000/110 V. The meter records 0.5 kWh. What is the actual energy?
- (a) 10 kWh
- (b) 100 kWh
- (c) 1,000 kWh
- (d) 5,000 kWh
Answer: (c) 1,000 kWh — multiplying factor = (100 ÷ 5) × (11,000 ÷ 110) = 20 × 100 = 2,000, so actual energy = 0.5 × 2,000 = 1,000 kWh.
Q6. A domestic single-phase energy meter is connected with how many wires?
- (a) One wire
- (b) Two wires (phase and neutral)
- (c) Three wires
- (d) Four wires
Answer: (b) Two wires (phase and neutral) — the meter is wired in series with the phase and the neutral passes through it.
Q7. Why are CTs used with energy meters in factories and large buildings?
- (a) To increase the meter’s voltage rating
- (b) Because the load current is too high to pass directly through the meter
- (c) To reduce the power factor
- (d) To protect the meter from lightning only
Answer: (b) Because the load current is too high to pass directly through the meter — the CT steps the current down (e.g. 200 A to 5 A) so a standard 5 A meter can measure it.
Q8. A CT of ratio 50/5 A feeds a meter that records 3 kWh. What is the actual energy used?
- (a) 3 kWh
- (b) 15 kWh
- (c) 30 kWh
- (d) 150 kWh
Answer: (c) 30 kWh — multiplying factor = 50 ÷ 5 = 10, so actual energy = 3 × 10 = 30 kWh.
Q9. In HT metering, a potential transformer (PT) is used to:
- (a) Step down the high voltage to a safe level (e.g. 110 V) for the meter
- (b) Increase the load current
- (c) Correct the power factor
- (d) Store energy for the meter
Answer: (a) Step down the high voltage to a safe level (e.g. 110 V) for the meter — the meter’s pressure coil cannot be connected directly to 11 kV.
Q10. A CT of ratio 400/5 A feeds a meter that records 1.5 kWh. What is the actual energy consumed?
- (a) 7.5 kWh
- (b) 60 kWh
- (c) 120 kWh
- (d) 600 kWh
Answer: (c) 120 kWh — multiplying factor = 400 ÷ 5 = 80, so actual energy = 1.5 × 80 = 120 kWh.
Also read: Watt Calculator | All MCQ Topics