DC Generator MCQs — Set 3
10 practice questions on shunt DC generators — how their voltage, field current and load behave.
Q1. How does the terminal voltage of a shunt DC generator change as the load increases?
- (a) It rises sharply
- (b) It falls slightly
- (c) It stays exactly constant
- (d) It falls to zero immediately
Answer: (b) It falls slightly — armature resistance drop and armature reaction reduce the terminal voltage as load current grows.
Q2. When the load on a shunt DC generator increases, its shunt field current:
- (a) Increases in proportion to the load
- (b) Falls to zero
- (c) Stays approximately constant
- (d) Reverses direction
Answer: (c) Stays approximately constant — the field is connected across the terminals, and terminal voltage changes only slightly with load.
Q3. A shunt generator has an armature current of 52 A and a shunt field current of 2 A. What is the load current?
- (a) 54 A
- (b) 50 A
- (c) 52 A
- (d) 26 A
Answer: (b) 50 A — IL = Ia − Ish = 52 − 2 = 50 A.
Q4. Shunt DC generators are best suited to which application?
- (a) Arc welding
- (b) Battery charging and lighting loads needing fairly constant voltage
- (c) Series arc lamps only
- (d) High-voltage transmission
Answer: (b) Battery charging and lighting loads needing fairly constant voltage — the shunt machine’s voltage stays nearly steady over a wide load range.
Q5. A shunt generator produces a generated EMF of 220 V. Its armature current is 15 A and armature resistance is 0.4 Ω. What is the terminal voltage (ignoring brush drop)?
- (a) 214 V
- (b) 226 V
- (c) 220 V
- (d) 206 V
Answer: (a) 214 V — V = Eg − IaRa = 220 − (15 × 0.4) = 220 − 6 = 214 V.
Q6. The shunt field winding is connected:
- (a) In series with the armature
- (b) Across the armature (in parallel with it)
- (c) Across the load only
- (d) To an external AC supply
Answer: (b) Across the armature (in parallel with it) — that is what “shunt” means: the field is in parallel with the armature.
Q7. A shunt generator delivers 20 A at a terminal voltage of 220 V. What is its output power?
- (a) 4,400 W
- (b) 11 W
- (c) 440 W
- (d) 44,000 W
Answer: (a) 4,400 W — P = V × I = 220 × 20 = 4,400 W.
Q8. If the shunt field circuit of a running shunt generator is suddenly opened, the terminal voltage will:
- (a) Rise sharply
- (b) Collapse to a small residual value
- (c) Stay the same
- (d) Reverse polarity
Answer: (b) Collapse to a small residual value — with no field current, only the residual magnetism remains to generate EMF.
Q9. A shunt field winding has a resistance of 55 Ω and is connected across a 110 V supply. What is the shunt field current?
- (a) 0.5 A
- (b) 2 A
- (c) 5 A
- (d) 55 A
Answer: (b) 2 A — Ish = V ÷ Rsh = 110 ÷ 55 = 2 A.
Q10. Why does the voltage of a shunt generator fall when the load increases?
- (a) The field current increases
- (b) The armature resistance drop (IaRa) grows and armature reaction weakens the flux
- (c) The speed of the prime mover increases
- (d) The commutator reverses polarity
Answer: (b) The armature resistance drop (IaRa) grows and armature reaction weakens the flux — both effects lower the terminal voltage as load current rises.