Contactor MCQs — Set 10
10 practice questions on contactor standards, life, maintenance and special types — vacuum and DC contactors, thermal rating and coil suppression — with answers and explanations.
Q1. Which IEC standard covers contactors and motor starters?
- (a) IEC 60364
- (b) IEC 60947-4-1
- (c) IEC 60076
- (d) IEC 61140
Answer: (b) IEC 60947-4-1 — it specifies the ratings, utilisation categories and tests for contactors and motor starters.
Q2. A contactor is rated 10 million mechanical operations but only 1 million electrical operations. Why is the electrical life lower?
- (a) The coil wears out faster on load
- (b) Arcing under load erodes the contacts, while mechanical operation alone causes almost no contact wear
- (c) The spring weakens under load
- (d) The enclosure overheats
Answer: (b) Arcing under load erodes the contacts, while mechanical operation alone causes almost no contact wear — every loaded break burns a little contact material away.
Q3. During maintenance, pitted or burnt silver contact tips should be handled how?
- (a) Filed smooth with a metal file
- (b) Replaced, because filing removes the silver coating and shortens contact life
- (c) Cleaned with sandpaper
- (d) Left as they are, since pitting improves contact
Answer: (b) Replaced, because filing removes the silver coating and shortens contact life — silver contacts are not dressed with a file.
Q4. Why must the contactor pole faces be kept clean and free of dust and rust?
- (a) To improve the overload setting
- (b) Dust and rust increase the air gap, causing humming, vibration and coil overheating
- (c) To reduce the coil voltage
- (d) To increase the arc chute size
Answer: (b) Dust and rust increase the air gap, causing humming, vibration and coil overheating — a dirty pole face stops the armature closing fully.
Q5. Where is a vacuum contactor mainly used?
- (a) Low-voltage lighting circuits only
- (b) Medium-voltage and frequent-switching duties, where the arc is extinguished in vacuum
- (c) DC battery circuits only
- (d) Single-phase domestic wiring
Answer: (b) Medium-voltage and frequent-switching duties, where the arc is extinguished in vacuum — vacuum interrupters give very long electrical life.
Q6. Why does a DC contactor need a special arc chute with magnetic blowout?
- (a) DC arcs are weaker than AC arcs
- (b) A DC arc has no natural current zero crossing, so it must be stretched and cooled to extinguish it
- (c) DC contactors have no coil
- (d) DC arcs extinguish by themselves at once
Answer: (b) A DC arc has no natural current zero crossing, so it must be stretched and cooled to extinguish it — on AC the current passes through zero 100 times a second and helps kill the arc.
Q7. What does the contactor rating “Ith” (conventional free-air thermal current) mean?
- (a) The maximum short-circuit current it can break
- (b) The maximum continuous current the contactor can carry without overheating in free air
- (c) The coil current at pick-up
- (d) The starting current of the motor
Answer: (b) The maximum continuous current the contactor can carry without overheating in free air — it is the thermal limit of the contactor frame.
Q8. A contactor is to be installed outdoors in a dusty yard. What must be provided?
- (a) A larger coil
- (b) A suitable IP-rated enclosure to protect it from dust and moisture
- (c) A smaller overload relay
- (d) An extra arc chute only
Answer: (b) A suitable IP-rated enclosure to protect it from dust and moisture — dust on the pole faces and terminals causes humming and failure.
Q9. What is the purpose of a coil suppressor (RC snubber or varistor) across a contactor coil?
- (a) To increase the coil voltage
- (b) To suppress the voltage spike produced when the coil is de-energised, protecting PLC outputs and nearby contacts
- (c) To make the contactor close faster
- (d) To reduce the main contact current
Answer: (b) To suppress the voltage spike produced when the coil is de-energised, protecting PLC outputs and nearby contacts — the collapsing magnetic field generates a high transient voltage.
Q10. What is meant by the breaking capacity of a contactor?
- (a) The current it can carry continuously
- (b) The maximum current it can safely interrupt without damage
- (c) The current it draws at pick-up
- (d) The current that welds its contacts
Answer: (b) The maximum current it can safely interrupt without damage — the making capacity is the current it can safely close onto, and both are defined by the utilisation category.