Contactor MCQs — Set 9

10 practice questions on DOL and star–delta starters and on contactor faults — chattering, welded contacts and single-phasing — with answers and explanations.

Q1. How many contactors does a direct-on-line (DOL) starter use?

  • (a) 1
  • (b) 2
  • (c) 3
  • (d) 4

Answer: (a) 1 — a single contactor connects the motor straight to the full supply voltage.

Q2. How many contactors does a star–delta starter use?

  • (a) 1
  • (b) 2
  • (c) 3 — main, star and delta
  • (d) 6

Answer: (c) 3 — main, star and delta — the main contactor stays on while the star contactor is replaced by the delta contactor.

Q3. In star connection on a 400 V supply, what voltage does each motor winding receive?

  • (a) 400 V
  • (b) 230 V
  • (c) 110 V
  • (d) 690 V

Answer: (b) 230 V — in star, winding voltage = line voltage ÷ √3 = 400 ÷ 1.732 = 231 V, about 230 V.

Q4. Compared with DOL starting, the starting current in a star–delta starter is reduced to about what?

  • (a) One-half of DOL starting current
  • (b) One-third of DOL starting current
  • (c) One-sixth of DOL starting current
  • (d) The same as DOL starting current

Answer: (b) One-third of DOL starting current — the lower winding voltage in star cuts both current and starting torque to one-third.

Q5. When does the timer switch a star–delta starter from star to delta?

  • (a) At the instant the start button is pressed
  • (b) After the motor has run up to near full speed, usually after a few seconds
  • (c) Only when the overload relay trips
  • (d) When the supply fails

Answer: (b) After the motor has run up to near full speed, usually after a few seconds — the timer is set to the motor run-up time.

Q6. A contactor chatters (buzzes and vibrates) when energised. What is the most likely cause?

  • (a) The motor is overloaded
  • (b) Low coil voltage or a loose connection in the control circuit
  • (c) The arc chute is too large
  • (d) The overload relay setting is too high

Answer: (b) Low coil voltage or a loose connection in the control circuit — the magnetic pull is too weak to hold the armature firmly closed.

Q7. What causes contactor main contacts to weld together?

  • (a) Normal switching at rated current
  • (b) Excessive current from overload or a short circuit, or switching far too frequently
  • (c) Low ambient temperature
  • (d) A clean pole face

Answer: (b) Excessive current from overload or a short circuit, or switching far too frequently — the heat melts the contact surfaces together.

Q8. A three-phase motor hums loudly, runs slowly and overheats. One contactor pole is not closing. What is this fault called?

  • (a) Short circuit
  • (b) Single-phasing
  • (c) Earth fault
  • (d) Overvoltage

Answer: (b) Single-phasing — the motor is running on only two phases, so it draws excess current in the remaining windings and overheats.

Q9. Why can a stuck armature burn out the contactor coil?

  • (a) The coil voltage rises
  • (b) The air gap stays open, so the coil inductance stays low and the coil keeps drawing high pick-up current
  • (c) The main contacts open
  • (d) The shading ring melts

Answer: (b) The air gap stays open, so the coil inductance stays low and the coil keeps drawing high pick-up current — the coil is only meant to carry that current briefly.

Q10. What happens if the star–delta timer changes to delta too early?

  • (a) The motor stops
  • (b) The motor draws a large current surge, almost like a DOL start
  • (c) The motor runs in reverse
  • (d) The coil voltage falls to zero

Answer: (b) The motor draws a large current surge, almost like a DOL start — the motor has not yet run up to speed, so the changeover defeats the purpose of star starting.