Contactor MCQs — Set 9
10 practice questions on DOL and star–delta starters and on contactor faults — chattering, welded contacts and single-phasing — with answers and explanations.
Q1. How many contactors does a direct-on-line (DOL) starter use?
- (a) 1
- (b) 2
- (c) 3
- (d) 4
Answer: (a) 1 — a single contactor connects the motor straight to the full supply voltage.
Q2. How many contactors does a star–delta starter use?
- (a) 1
- (b) 2
- (c) 3 — main, star and delta
- (d) 6
Answer: (c) 3 — main, star and delta — the main contactor stays on while the star contactor is replaced by the delta contactor.
Q3. In star connection on a 400 V supply, what voltage does each motor winding receive?
- (a) 400 V
- (b) 230 V
- (c) 110 V
- (d) 690 V
Answer: (b) 230 V — in star, winding voltage = line voltage ÷ √3 = 400 ÷ 1.732 = 231 V, about 230 V.
Q4. Compared with DOL starting, the starting current in a star–delta starter is reduced to about what?
- (a) One-half of DOL starting current
- (b) One-third of DOL starting current
- (c) One-sixth of DOL starting current
- (d) The same as DOL starting current
Answer: (b) One-third of DOL starting current — the lower winding voltage in star cuts both current and starting torque to one-third.
Q5. When does the timer switch a star–delta starter from star to delta?
- (a) At the instant the start button is pressed
- (b) After the motor has run up to near full speed, usually after a few seconds
- (c) Only when the overload relay trips
- (d) When the supply fails
Answer: (b) After the motor has run up to near full speed, usually after a few seconds — the timer is set to the motor run-up time.
Q6. A contactor chatters (buzzes and vibrates) when energised. What is the most likely cause?
- (a) The motor is overloaded
- (b) Low coil voltage or a loose connection in the control circuit
- (c) The arc chute is too large
- (d) The overload relay setting is too high
Answer: (b) Low coil voltage or a loose connection in the control circuit — the magnetic pull is too weak to hold the armature firmly closed.
Q7. What causes contactor main contacts to weld together?
- (a) Normal switching at rated current
- (b) Excessive current from overload or a short circuit, or switching far too frequently
- (c) Low ambient temperature
- (d) A clean pole face
Answer: (b) Excessive current from overload or a short circuit, or switching far too frequently — the heat melts the contact surfaces together.
Q8. A three-phase motor hums loudly, runs slowly and overheats. One contactor pole is not closing. What is this fault called?
- (a) Short circuit
- (b) Single-phasing
- (c) Earth fault
- (d) Overvoltage
Answer: (b) Single-phasing — the motor is running on only two phases, so it draws excess current in the remaining windings and overheats.
Q9. Why can a stuck armature burn out the contactor coil?
- (a) The coil voltage rises
- (b) The air gap stays open, so the coil inductance stays low and the coil keeps drawing high pick-up current
- (c) The main contacts open
- (d) The shading ring melts
Answer: (b) The air gap stays open, so the coil inductance stays low and the coil keeps drawing high pick-up current — the coil is only meant to carry that current briefly.
Q10. What happens if the star–delta timer changes to delta too early?
- (a) The motor stops
- (b) The motor draws a large current surge, almost like a DOL start
- (c) The motor runs in reverse
- (d) The coil voltage falls to zero
Answer: (b) The motor draws a large current surge, almost like a DOL start — the motor has not yet run up to speed, so the changeover defeats the purpose of star starting.