Contactor MCQs — Set 4

10 practice questions on contactor utilisation categories — AC-1, AC-2, AC-3, AC-4 and DC-1 — with answers and explanations.

Q1. Utilisation category AC-1 is meant for which type of load?

  • (a) Squirrel-cage motors during starting
  • (b) Non-inductive or slightly inductive loads such as heaters and lamps
  • (c) Slip-ring motors
  • (d) Plugging and inching of motors

Answer: (b) Non-inductive or slightly inductive loads such as heaters and lamps — AC-1 covers resistive loads with no high starting current.

Q2. Utilisation category AC-3 is meant for which type of load?

  • (a) Resistive heaters
  • (b) Squirrel-cage motors: starting and switching off a running motor
  • (c) DC shunt motors
  • (d) Capacitor banks only

Answer: (b) Squirrel-cage motors: starting and switching off a running motor — AC-3 is the standard motor-duty rating.

Q3. Utilisation category AC-4 is meant for which duty?

  • (a) Normal starting of a squirrel-cage motor
  • (b) Resistive heating loads
  • (c) Plugging, inching and reversing of squirrel-cage motors
  • (d) Switching off a transformer at no load

Answer: (c) Plugging, inching and reversing of squirrel-cage motors — AC-4 is severe duty with very high making and breaking currents.

Q4. Which utilisation category is the most severe duty for a contactor?

  • (a) AC-1
  • (b) AC-2
  • (c) AC-3
  • (d) AC-4

Answer: (d) AC-4 — plugging and inching break currents several times the motor full-load current, so contact wear is highest.

Q5. A contactor is rated 25 A AC-3 but 40 A AC-1. Why is the AC-1 rating higher?

  • (a) Resistive loads draw a high starting current
  • (b) Resistive loads have no high starting current and no inductive kick, so the contacts suffer less
  • (c) AC-1 is measured at a lower voltage
  • (d) The coil is larger for AC-1 duty

Answer: (b) Resistive loads have no high starting current and no inductive kick, so the contacts suffer less — the same contacts can therefore carry more AC-1 current.

Q6. Which load should be selected using the AC-1 rating?

  • (a) A 7.5 kW squirrel-cage motor
  • (b) A 9 kW three-phase heater bank
  • (c) A crane motor used for inching
  • (d) A slip-ring motor

Answer: (b) A 9 kW three-phase heater bank — heaters are resistive loads, so the AC-1 rating applies.

Q7. A 7.5 kW, 400 V, three-phase motor has a full-load current of 13.5 A. What is the minimum AC-3 rating of the contactor?

  • (a) 9 A
  • (b) 12 A
  • (c) 18 A
  • (d) 32 A

Answer: (c) 18 A — the AC-3 rating must be at least the motor full-load current of 13.5 A, and 18 A is the next standard size above it (12 A is too small).

Q8. AC-4 duty is typically found in which application?

  • (a) A water heater switched once a day
  • (b) A crane or lift motor that is inched and plugged repeatedly
  • (c) Street lighting switched by a timer
  • (d) A fan running continuously

Answer: (b) A crane or lift motor that is inched and plugged repeatedly — frequent plugging and inching is exactly the severe AC-4 duty.

Q9. Utilisation category DC-1 is for which type of load?

  • (a) DC series motors
  • (b) Resistive DC loads
  • (c) AC squirrel-cage motors
  • (d) DC shunt motors during plugging

Answer: (b) Resistive DC loads — DC-1 covers non-inductive DC loads, while DC-3 and DC-5 cover DC motors.

Q10. Utilisation category AC-2 is for which type of motor?

  • (a) Squirrel-cage motors
  • (b) Slip-ring (wound-rotor) motors: starting and switching off
  • (c) Single-phase capacitor motors
  • (d) Synchronous motors

Answer: (b) Slip-ring (wound-rotor) motors: starting and switching off — AC-2 is the wound-rotor equivalent of AC-3.

Also read: Power Loss Calculator | Power and Energy MCQs | All MCQ Topics