Contactor MCQs — Set 3
10 practice questions on contactor coils — voltage ratings, pick-up and holding current, the shading ring and humming — with answers and explanations.
Q1. Which coil voltage is commonly used for safe low-voltage control circuits?
- (a) 400 V
- (b) 230 V
- (c) 24 V
- (d) 11 kV
Answer: (c) 24 V — a 24 V control circuit is safer for operators and for PLC outputs than mains-voltage control.
Q2. What happens if the coil voltage is much lower than the rated coil voltage?
- (a) The contactor picks up faster
- (b) The contactor chatters or fails to pick up, and the contacts may burn
- (c) The coil burns out at once
- (d) The overload relay trips
Answer: (b) The contactor chatters or fails to pick up, and the contacts may burn — the magnetic pull is too weak to hold the armature firmly closed.
Q3. What happens if the coil voltage is much higher than the rated coil voltage?
- (a) The contactor works normally
- (b) The contacts weld together
- (c) The coil draws excessive current, overheats and burns out
- (d) The main contacts open
Answer: (c) The coil draws excessive current, overheats and burns out — coil insulation fails when the voltage is well above rating.
Q4. Loud humming from an AC contactor usually indicates what?
- (a) The overload relay has tripped
- (b) A broken shading ring, dust on the pole faces, or low coil voltage
- (c) The motor is overloaded
- (d) The arc chute is missing
Answer: (b) A broken shading ring, dust on the pole faces, or low coil voltage — any of these lets the armature vibrate at mains frequency.
Q5. Why does a DC-coil contactor not hum like an AC-coil contactor?
- (a) It has no armature
- (b) DC produces a steady magnetic flux, so there is no alternating pull on the armature
- (c) It has no coil
- (d) It switches only resistive loads
Answer: (b) DC produces a steady magnetic flux, so there is no alternating pull on the armature — humming comes from flux rising and falling every half-cycle on AC.
Q6. How does the coil current change after the contactor closes?
- (a) It stays the same
- (b) It rises sharply
- (c) It falls, because the closed air gap raises the coil inductance
- (d) It falls to zero
Answer: (c) It falls, because the closed air gap raises the coil inductance — the pick-up current is much higher than the holding current.
Q7. Where is the contactor coil connected?
- (a) In series with the motor in the power circuit
- (b) In the control circuit, across the control supply, through the start–stop buttons
- (c) Across the main contacts
- (d) In parallel with the overload relay heater
Answer: (b) In the control circuit, across the control supply, through the start–stop buttons — the coil is a control load, not part of the power circuit.
Q8. What is the shading ring (shading coil) in an AC contactor for?
- (a) To cool the coil
- (b) To keep part of the magnetic flux from falling to zero each half-cycle, preventing chattering
- (c) To extinguish the arc on the main contacts
- (d) To increase the coil voltage
Answer: (b) To keep part of the magnetic flux from falling to zero each half-cycle, preventing chattering — the shorted copper ring creates a delayed flux in part of the pole face.
Q9. What happens if an AC-rated coil is connected to a DC supply of the same voltage?
- (a) It works normally
- (b) It draws excessive current and burns out, because on DC only the low winding resistance limits the current
- (c) It hums loudly
- (d) It picks up more slowly
Answer: (b) It draws excessive current and burns out, because on DC only the low winding resistance limits the current — on AC, the inductance limits the current.
Q10. A motor runs on a 400 V supply but the control circuit is 110 V. Which coil should the contactor have?
- (a) 400 V coil
- (b) 230 V coil
- (c) 110 V coil
- (d) 24 V coil
Answer: (c) 110 V coil — the coil voltage must match the control-circuit supply, not the motor supply voltage.