Contactor MCQs — Set 3

10 practice questions on contactor coils — voltage ratings, pick-up and holding current, the shading ring and humming — with answers and explanations.

Q1. Which coil voltage is commonly used for safe low-voltage control circuits?

  • (a) 400 V
  • (b) 230 V
  • (c) 24 V
  • (d) 11 kV

Answer: (c) 24 V — a 24 V control circuit is safer for operators and for PLC outputs than mains-voltage control.

Q2. What happens if the coil voltage is much lower than the rated coil voltage?

  • (a) The contactor picks up faster
  • (b) The contactor chatters or fails to pick up, and the contacts may burn
  • (c) The coil burns out at once
  • (d) The overload relay trips

Answer: (b) The contactor chatters or fails to pick up, and the contacts may burn — the magnetic pull is too weak to hold the armature firmly closed.

Q3. What happens if the coil voltage is much higher than the rated coil voltage?

  • (a) The contactor works normally
  • (b) The contacts weld together
  • (c) The coil draws excessive current, overheats and burns out
  • (d) The main contacts open

Answer: (c) The coil draws excessive current, overheats and burns out — coil insulation fails when the voltage is well above rating.

Q4. Loud humming from an AC contactor usually indicates what?

  • (a) The overload relay has tripped
  • (b) A broken shading ring, dust on the pole faces, or low coil voltage
  • (c) The motor is overloaded
  • (d) The arc chute is missing

Answer: (b) A broken shading ring, dust on the pole faces, or low coil voltage — any of these lets the armature vibrate at mains frequency.

Q5. Why does a DC-coil contactor not hum like an AC-coil contactor?

  • (a) It has no armature
  • (b) DC produces a steady magnetic flux, so there is no alternating pull on the armature
  • (c) It has no coil
  • (d) It switches only resistive loads

Answer: (b) DC produces a steady magnetic flux, so there is no alternating pull on the armature — humming comes from flux rising and falling every half-cycle on AC.

Q6. How does the coil current change after the contactor closes?

  • (a) It stays the same
  • (b) It rises sharply
  • (c) It falls, because the closed air gap raises the coil inductance
  • (d) It falls to zero

Answer: (c) It falls, because the closed air gap raises the coil inductance — the pick-up current is much higher than the holding current.

Q7. Where is the contactor coil connected?

  • (a) In series with the motor in the power circuit
  • (b) In the control circuit, across the control supply, through the start–stop buttons
  • (c) Across the main contacts
  • (d) In parallel with the overload relay heater

Answer: (b) In the control circuit, across the control supply, through the start–stop buttons — the coil is a control load, not part of the power circuit.

Q8. What is the shading ring (shading coil) in an AC contactor for?

  • (a) To cool the coil
  • (b) To keep part of the magnetic flux from falling to zero each half-cycle, preventing chattering
  • (c) To extinguish the arc on the main contacts
  • (d) To increase the coil voltage

Answer: (b) To keep part of the magnetic flux from falling to zero each half-cycle, preventing chattering — the shorted copper ring creates a delayed flux in part of the pole face.

Q9. What happens if an AC-rated coil is connected to a DC supply of the same voltage?

  • (a) It works normally
  • (b) It draws excessive current and burns out, because on DC only the low winding resistance limits the current
  • (c) It hums loudly
  • (d) It picks up more slowly

Answer: (b) It draws excessive current and burns out, because on DC only the low winding resistance limits the current — on AC, the inductance limits the current.

Q10. A motor runs on a 400 V supply but the control circuit is 110 V. Which coil should the contactor have?

  • (a) 400 V coil
  • (b) 230 V coil
  • (c) 110 V coil
  • (d) 24 V coil

Answer: (c) 110 V coil — the coil voltage must match the control-circuit supply, not the motor supply voltage.