Compressor MCQs — Set 5
10 practice questions on compressor motors, starting methods and overload protection, with worked answers.
Q1. A 1 HP single-phase compressor motor runs on 230 V at a power factor of 0.8. What is its full-load current?
- (a) 2.03 A
- (b) 4.05 A
- (c) 8.11 A
- (d) 12.16 A
Answer: (b) 4.05 A — I = 746 ÷ (230 × 0.8) = 746 ÷ 184 = 4.05 A.
Q2. A 2 HP single-phase compressor motor runs on 230 V at a power factor of 0.8. What is its full-load current?
- (a) 4.05 A
- (b) 6.08 A
- (c) 8.11 A
- (d) 16.22 A
Answer: (c) 8.11 A — power is 2 × 746 = 1,492 W, so I = 1,492 ÷ (230 × 0.8) = 1,492 ÷ 184 = 8.11 A.
Q3. Why is a capacitor-start motor commonly used for single-phase compressors?
- (a) It uses less oil
- (b) It gives the high starting torque needed to start against compression load
- (c) It runs without a capacitor
- (d) It needs no overload protection
Answer: (b) It gives the high starting torque needed to start against compression load — a plain single-phase motor has very low starting torque.
Q4. Roughly how large is the starting current of an induction motor compared with its full-load current?
- (a) About the same as full-load current
- (b) About half the full-load current
- (c) About 5 to 7 times the full-load current
- (d) About 20 times the full-load current
Answer: (c) About 5 to 7 times the full-load current — this is why breakers and starters must allow for the starting surge.
Q5. When does an overload relay trip?
- (a) The instant the motor is switched on
- (b) When the current stays above its setting for a period of time
- (c) When the voltage rises
- (d) When the air pressure rises
Answer: (b) When the current stays above its setting for a period of time — it tolerates the brief starting surge but trips on sustained overload.
Q6. A direct-on-line (DOL) starter is suitable for which compressors?
- (a) Only very large three-phase compressors
- (b) Small single-phase and small-horsepower compressors, where the full starting current is acceptable
- (c) Compressors with no motor
- (d) Only refrigeration compressors
Answer: (b) Small single-phase and small-horsepower compressors, where the full starting current is acceptable — large motors need reduced-voltage starting.
Q7. A star-delta starter reduces the starting current of a three-phase motor to about what fraction of the direct-on-line value?
- (a) One-half
- (b) One-third
- (c) One-tenth
- (d) It does not reduce it at all
Answer: (b) One-third — the motor starts in star with lower voltage per winding, then switches to delta for full running power.
Q8. A single-phase compressor hums loudly but will not start. What is the most likely cause?
- (a) A failed start capacitor
- (b) A clogged air filter
- (c) A full receiver tank
- (d) Low refrigerant charge
Answer: (a) A failed start capacitor — without the capacitor the motor cannot develop starting torque, so it just hums and draws locked-rotor current.
Q9. Why is a compressor motor fitted with an internal thermal overload protector?
- (a) To stop the motor if its windings overheat, for example from a stalled rotor or low voltage
- (b) To increase the starting torque
- (c) To reduce the running current
- (d) To filter the refrigerant
Answer: (a) To stop the motor if its windings overheat, for example from a stalled rotor or low voltage — the protector opens the circuit when the windings get too hot, before the motor burns out.
Q10. A 5 kW compressor motor runs on 230 V at a power factor of 0.9. What current does it draw?
- (a) 12.1 A
- (b) 21.7 A
- (c) 24.2 A
- (d) 48.3 A
Answer: (c) 24.2 A — I = 5,000 ÷ (230 × 0.9) = 5,000 ÷ 207 = 24.2 A.