Circuit Breaker Types MCQs — Set 10
10 practice questions on advanced breaker topics — RCBOs, selectivity, standards, accessories and arc control. Work each one out before checking the answer.
Q1. What does discrimination (selectivity) between two breakers mean?
- (a) Only the breaker nearest the fault trips, while the upstream breaker stays on
- (b) Both breakers always trip together
- (c) The upstream breaker always trips first
- (d) Breakers are sorted by colour
Answer: (a) Only the breaker nearest the fault trips, while the upstream breaker stays on — good selectivity keeps the healthy circuits running during a fault on one circuit.
Q2. What protection does an RCBO provide?
- (a) Overload and short-circuit protection only
- (b) Earth leakage protection only
- (c) Overload, short-circuit AND earth leakage protection in one device
- (d) Surge protection only
Answer: (c) Overload, short-circuit AND earth leakage protection in one device — an RCBO combines an MCB and an RCCB, typically with 30 mA earth leakage protection.
Q3. What is the key difference between an RCCB and an MCB?
- (a) An RCCB detects earth leakage current; an MCB detects overload and short circuit
- (b) An RCCB protects against overload and an MCB against earth leakage
- (c) There is no difference — they are the same device
- (d) An RCCB works only on DC supplies
Answer: (a) An RCCB detects earth leakage current; an MCB detects overload and short circuit — an RCCB alone gives no overload protection, so it is used with an MCB or fuse.
Q4. What is the standard earth leakage trip sensitivity of an RCCB used for personal protection in homes?
- (a) 300 mA
- (b) 30 mA
- (c) 3 A
- (d) 100 A
Answer: (b) 30 mA — a 30 mA RCCB trips fast enough on a small leakage to protect a person from a dangerous shock.
Q5. How does an isolator (disconnector) differ from a circuit breaker?
- (a) An isolator only disconnects a dead circuit for safe maintenance; it cannot interrupt fault current
- (b) An isolator trips faster than any breaker
- (c) An isolator protects against overload
- (d) There is no difference
Answer: (a) An isolator only disconnects a dead circuit for safe maintenance; it cannot interrupt fault current — it must be opened only after the load is switched off.
Q6. What is the purpose of the arc chute inside a breaker?
- (a) To split the arc into smaller arcs, cool it and extinguish it quickly as the contacts open
- (b) To increase the arc temperature
- (c) To store the arc energy for later use
- (d) To hold the contacts closed
Answer: (a) To split the arc into smaller arcs, cool it and extinguish it quickly as the contacts open — metal plates in the chute divide and cool the arc until it dies.
Q7. What is a shunt trip, and how does it differ from an undervoltage release?
- (a) A shunt trip opens the breaker when an external signal energises its coil; an undervoltage release trips it when the supply voltage falls
- (b) Both do exactly the same thing
- (c) A shunt trip increases the voltage and an undervoltage release decreases it
- (d) A shunt trip works only on DC
Answer: (a) A shunt trip opens the breaker when an external signal energises its coil; an undervoltage release trips it when the supply voltage falls — one is commanded, the other reacts to voltage loss.
Q8. What is an auxiliary contact on a circuit breaker used for?
- (a) Remote indication and signalling of whether the breaker is open or closed
- (b) Carrying the main load current
- (c) Increasing the breaking capacity
- (d) Cooling the breaker
Answer: (a) Remote indication and signalling of whether the breaker is open or closed — auxiliary contacts drive lamps, alarms or control systems.
Q9. Which standard covers MCBs for household use, and which covers industrial breakers such as MCCBs and ACBs?
- (a) IEC 60898 for household MCBs; IEC 60947-2 for industrial MCCBs and ACBs
- (b) IEC 60947-2 for household MCBs; IEC 60898 for industrial breakers
- (c) Both are covered by the same standard with no difference
- (d) No standard covers circuit breakers
Answer: (a) IEC 60898 for household MCBs; IEC 60947-2 for industrial MCCBs and ACBs — the two standards reflect the different duties and test requirements.
Q10. A 25 A D-curve MCB trips magnetically at what current range?
- (a) 75–125 A
- (b) 125–250 A
- (c) 250–500 A
- (d) 500–1,000 A
Answer: (c) 250–500 A — D curve is 10–20× rated current, so 25 × 10 = 250 A and 25 × 20 = 500 A.