Circuit Breaker Types MCQs — Set 9

10 practice questions on breaker testing and maintenance — why breakers trip, how to test them, and when to replace one. Work each one out before checking the answer.

Q1. An MCB keeps tripping again and again. What is the correct first action?

  • (a) Keep resetting it until it stays on
  • (b) Find and fix the cause — overload, short circuit or faulty appliance — before resetting
  • (c) Fit a breaker of double the rating
  • (d) Remove the breaker and join the wires together

Answer: (b) Find and fix the cause — overload, short circuit or faulty appliance — before resetting — repeated resetting on a live fault risks fire and breaker damage.

Q2. How is the trip function of an MCB verified during professional testing?

  • (a) By pressing a test button on the MCB
  • (b) With a primary injection test set that passes a known current through the breaker
  • (c) By shorting the output terminals with a wire
  • (d) It cannot be tested at all

Answer: (b) With a primary injection test set that passes a known current through the breaker — unlike an RCCB, an MCB has no test button, so a test set checks its actual trip current and time.

Q3. How often should the test button on an RCCB be pressed to check it still works?

  • (a) Once a year
  • (b) Monthly
  • (c) Once every 10 years
  • (d) Never — pressing it damages the RCCB

Answer: (b) Monthly — the test button simulates an earth fault; monthly testing catches a stuck mechanism before a real fault occurs.

Q4. A loose terminal screw on a breaker causes what problem?

  • (a) Higher contact resistance, heating, and possible nuisance tripping or burning
  • (b) A higher supply voltage
  • (c) Faster tripping on earth faults only
  • (d) No problem at all

Answer: (a) Higher contact resistance, heating, and possible nuisance tripping or burning — a loose connection heats up under load (I²R) and can scorch the breaker and cable.

Q5. After a breaker trips on a short circuit, what should be done before it is switched back on?

  • (a) Inspect the breaker and wiring for damage, burning or smell, and clear the fault
  • (b) Switch it on at once with no checks
  • (c) Spray water on the breaker to cool it
  • (d) Tighten the screws while the supply is still on

Answer: (a) Inspect the breaker and wiring for damage, burning or smell, and clear the fault — a short circuit can damage contacts and insulation that must be checked first.

Q6. What is the purpose of a contact resistance test (micro-ohmmeter) on a breaker?

  • (a) To check that the closed contacts have low resistance and are not pitted or corroded
  • (b) To measure the supply voltage
  • (c) To test the earth leakage current
  • (d) To set the tripping curve

Answer: (a) To check that the closed contacts have low resistance and are not pitted or corroded — high contact resistance causes overheating under load.

Q7. Which sign shows a breaker probably needs replacing?

  • (a) It is slightly dusty
  • (b) Burnt smell, discoloration, cracked case, or it will not stay switched on
  • (c) It has been in service for one month
  • (d) Its handle is in the ON position

Answer: (b) Burnt smell, discoloration, cracked case, or it will not stay switched on — these are signs of internal damage or worn contacts.

Q8. Why should breaker terminal screws be tightened to the manufacturer’s specified torque?

  • (a) Over-tightening can crack the terminal or strip the thread, while under-tightening leaves a loose, heating connection
  • (b) Torque does not matter for breakers
  • (c) Torque settings only apply to fuses
  • (d) Tightening harder always improves protection

Answer: (a) Over-tightening can crack the terminal or strip the thread, while under-tightening leaves a loose, heating connection — the specified torque gives a firm connection without damage.

Q9. Why does a VCB generally need less routine maintenance than an oil breaker?

  • (a) Its contacts are sealed in a vacuum bottle with very little wear and there is no oil to filter or replace
  • (b) A VCB has no contacts at all
  • (c) A VCB never carries any current
  • (d) Oil breakers are sealed for life

Answer: (a) Its contacts are sealed in a vacuum bottle with very little wear and there is no oil to filter or replace — the sealed interrupter is the main reason for the VCB’s long service intervals.

Q10. Before re-energising a circuit after fault repairs, which test checks that the insulation is sound?

  • (a) An insulation resistance test with a megger
  • (b) A voltage test with a neon screwdriver only
  • (c) A continuity test of the earth wire only
  • (d) No test is needed after any repair

Answer: (a) An insulation resistance test with a megger — it applies a high DC voltage and confirms the insulation resistance is high enough to be safe.