Circuit Breaker Types MCQs — Set 7
10 practice questions on thermal vs magnetic tripping — how a breaker tells a slow overload from a sudden short circuit. Work each one out before checking the answer.
Q1. Which fault does the thermal trip of an MCB protect against?
- (a) Short circuit
- (b) Sustained overload
- (c) Earth leakage
- (d) Lightning surge
Answer: (b) Sustained overload — the bimetallic strip heats up slowly, so it responds to a current that stays above rating for some time.
Q2. Which fault does the magnetic trip of an MCB protect against?
- (a) Sustained overload
- (b) Short circuit
- (c) Undervoltage
- (d) Earth leakage of 30 mA
Answer: (b) Short circuit — the solenoid reacts instantly to the very large current of a short circuit.
Q3. A circuit draws 1.5 times the MCB rating for several minutes. What happens?
- (a) The magnetic trip fires instantly
- (b) The thermal trip operates after a time delay
- (c) Nothing ever happens
- (d) The breaker explodes immediately
Answer: (b) The thermal trip operates after a time delay — a modest overload needs time to heat the bimetallic strip, so the trip is delayed, not instant.
Q4. A dead short circuit draws about 100 times the MCB rating. What happens?
- (a) The thermal trip operates after several minutes
- (b) The magnetic trip operates almost instantly, in milliseconds
- (c) The breaker waits for the load to cool
- (d) The RCCB trips instead
Answer: (b) The magnetic trip operates almost instantly, in milliseconds — the solenoid’s strong pull releases the mechanism at once, limiting damage.
Q5. Why does a breaker need both a thermal and a magnetic trip?
- (a) Overloads need a delay so brief inrushes do not trip it, while short circuits need instant clearing
- (b) One trip is a spare in case the other breaks
- (c) The thermal trip works on DC and the magnetic on AC
- (d) To double the rated current
Answer: (a) Overloads need a delay so brief inrushes do not trip it, while short circuits need instant clearing — the two elements cover two very different fault speeds.
Q6. What heats the bimetallic strip in the thermal trip?
- (a) The supply voltage alone
- (b) I²R heating from the load current flowing through it
- (c) Heat from the sun
- (d) Friction from the switch handle
Answer: (b) I²R heating from the load current flowing through it — heating rises with the square of the current, so a bigger overload heats it much faster.
Q7. What does an inverse-time tripping characteristic mean?
- (a) The higher the fault current, the faster the breaker trips
- (b) The breaker always trips after exactly 10 seconds
- (c) The breaker trips slower as current rises
- (d) The breaker never trips on overload
Answer: (a) The higher the fault current, the faster the breaker trips — a small overload may take minutes, while a large one trips in seconds.
Q8. How can a very hot ambient temperature affect an MCB’s thermal trip?
- (a) It has no effect at all
- (b) The breaker may trip earlier, at a lower current, because the bimetallic strip is already warm
- (c) The breaker will never trip
- (d) The rated current doubles
Answer: (b) The breaker may trip earlier, at a lower current, because the bimetallic strip is already warm — thermal trips are temperature-sensitive, so ratings assume a standard ambient temperature.
Q9. In a thermal-magnetic MCCB, which element gives the adjustable long-time (overload) setting?
- (a) The thermal element
- (b) The magnetic element only
- (c) The arc chute
- (d) The shunt trip coil
Answer: (a) The thermal element — the long-time pickup and delay are set on the thermal (overload) side, while the magnetic side sets the instant short-circuit pickup.
Q10. A motor starts and draws 6 times its rated current for 2 seconds. Why does a correctly chosen breaker NOT trip?
- (a) The thermal trip is too slow to react to a 2-second inrush and the current is below the magnetic pickup
- (b) Motors never draw starting current
- (c) The breaker is switched off during starting
- (d) The magnetic trip only works on overloads
Answer: (a) The thermal trip is too slow to react to a 2-second inrush and the current is below the magnetic pickup — with a D-curve (10–20×) breaker, a 6× inrush stays below the magnetic threshold.