Circuit Breaker Types MCQs — Set 7

10 practice questions on thermal vs magnetic tripping — how a breaker tells a slow overload from a sudden short circuit. Work each one out before checking the answer.

Q1. Which fault does the thermal trip of an MCB protect against?

  • (a) Short circuit
  • (b) Sustained overload
  • (c) Earth leakage
  • (d) Lightning surge

Answer: (b) Sustained overload — the bimetallic strip heats up slowly, so it responds to a current that stays above rating for some time.

Q2. Which fault does the magnetic trip of an MCB protect against?

  • (a) Sustained overload
  • (b) Short circuit
  • (c) Undervoltage
  • (d) Earth leakage of 30 mA

Answer: (b) Short circuit — the solenoid reacts instantly to the very large current of a short circuit.

Q3. A circuit draws 1.5 times the MCB rating for several minutes. What happens?

  • (a) The magnetic trip fires instantly
  • (b) The thermal trip operates after a time delay
  • (c) Nothing ever happens
  • (d) The breaker explodes immediately

Answer: (b) The thermal trip operates after a time delay — a modest overload needs time to heat the bimetallic strip, so the trip is delayed, not instant.

Q4. A dead short circuit draws about 100 times the MCB rating. What happens?

  • (a) The thermal trip operates after several minutes
  • (b) The magnetic trip operates almost instantly, in milliseconds
  • (c) The breaker waits for the load to cool
  • (d) The RCCB trips instead

Answer: (b) The magnetic trip operates almost instantly, in milliseconds — the solenoid’s strong pull releases the mechanism at once, limiting damage.

Q5. Why does a breaker need both a thermal and a magnetic trip?

  • (a) Overloads need a delay so brief inrushes do not trip it, while short circuits need instant clearing
  • (b) One trip is a spare in case the other breaks
  • (c) The thermal trip works on DC and the magnetic on AC
  • (d) To double the rated current

Answer: (a) Overloads need a delay so brief inrushes do not trip it, while short circuits need instant clearing — the two elements cover two very different fault speeds.

Q6. What heats the bimetallic strip in the thermal trip?

  • (a) The supply voltage alone
  • (b) I²R heating from the load current flowing through it
  • (c) Heat from the sun
  • (d) Friction from the switch handle

Answer: (b) I²R heating from the load current flowing through it — heating rises with the square of the current, so a bigger overload heats it much faster.

Q7. What does an inverse-time tripping characteristic mean?

  • (a) The higher the fault current, the faster the breaker trips
  • (b) The breaker always trips after exactly 10 seconds
  • (c) The breaker trips slower as current rises
  • (d) The breaker never trips on overload

Answer: (a) The higher the fault current, the faster the breaker trips — a small overload may take minutes, while a large one trips in seconds.

Q8. How can a very hot ambient temperature affect an MCB’s thermal trip?

  • (a) It has no effect at all
  • (b) The breaker may trip earlier, at a lower current, because the bimetallic strip is already warm
  • (c) The breaker will never trip
  • (d) The rated current doubles

Answer: (b) The breaker may trip earlier, at a lower current, because the bimetallic strip is already warm — thermal trips are temperature-sensitive, so ratings assume a standard ambient temperature.

Q9. In a thermal-magnetic MCCB, which element gives the adjustable long-time (overload) setting?

  • (a) The thermal element
  • (b) The magnetic element only
  • (c) The arc chute
  • (d) The shunt trip coil

Answer: (a) The thermal element — the long-time pickup and delay are set on the thermal (overload) side, while the magnetic side sets the instant short-circuit pickup.

Q10. A motor starts and draws 6 times its rated current for 2 seconds. Why does a correctly chosen breaker NOT trip?

  • (a) The thermal trip is too slow to react to a 2-second inrush and the current is below the magnetic pickup
  • (b) Motors never draw starting current
  • (c) The breaker is switched off during starting
  • (d) The magnetic trip only works on overloads

Answer: (a) The thermal trip is too slow to react to a 2-second inrush and the current is below the magnetic pickup — with a D-curve (10–20×) breaker, a 6× inrush stays below the magnetic threshold.