Cable Types MCQs — Set 6
10 worked voltage-drop problems for single-phase cable runs — loop resistance, volts lost and the 5% limit.
Q1. A 20 A load is fed by a 25 m run of 2.5 mm² copper cable (7.41 Ω/km). The loop resistance is 2 × 25 × 7.41 ÷ 1,000 = 0.371 Ω, so the drop is 7.41 V. What is this as a percentage of 230 V?
- (a) 1.0%
- (b) 2.0%
- (c) 3.2%
- (d) 5.0%
Answer: (c) 3.2% — 7.41 ÷ 230 × 100 = 3.2%, which is inside the 5% limit.
Q2. A 20 A load is fed by a 25 m run of 4 mm² copper cable (4.61 Ω/km). The loop resistance is 0.231 Ω, so the drop is 4.61 V. What is this as a percentage of 230 V?
- (a) 2.0%
- (b) 3.2%
- (c) 1.0%
- (d) 5.1%
Answer: (a) 2.0% — 4.61 ÷ 230 × 100 = 2.0%, comfortably inside the limit, and better than the 2.5 mm² run in Q1.
Q3. A 30 A load is fed by a 20 m run of 4 mm² copper cable (4.61 Ω/km). The drop is 5.53 V. What is this as a percentage of 230 V?
- (a) 1.5%
- (b) 2.4%
- (c) 3.4%
- (d) 5.0%
Answer: (b) 2.4% — loop R = 2 × 20 × 4.61 ÷ 1,000 = 0.184 Ω, drop = 30 × 0.184 = 5.53 V, and 5.53 ÷ 230 × 100 = 2.4%.
Q4. A 10 A load is fed by a 30 m run of 1.5 mm² copper cable (12.1 Ω/km). What is the voltage drop?
- (a) 3.63 V
- (b) 7.26 V
- (c) 14.5 V
- (d) 1.21 V
Answer: (b) 7.26 V — loop R = 2 × 30 × 12.1 ÷ 1,000 = 0.726 Ω, drop = 10 × 0.726 = 7.26 V (3.2% of 230 V).
Q5. A 16 A load is fed by a 20 m run of 2.5 mm² copper cable (7.41 Ω/km). What is the voltage drop?
- (a) 2.37 V
- (b) 4.74 V
- (c) 9.48 V
- (d) 1.48 V
Answer: (b) 4.74 V — loop R = 2 × 20 × 7.41 ÷ 1,000 = 0.296 Ω, drop = 16 × 0.296 = 4.74 V (2.1% of 230 V).
Q6. A 25 A load is fed by a 15 m run of 6 mm² copper cable (3.08 Ω/km). What is the voltage drop?
- (a) 1.16 V
- (b) 2.31 V
- (c) 4.62 V
- (d) 0.58 V
Answer: (b) 2.31 V — loop R = 2 × 15 × 3.08 ÷ 1,000 = 0.0924 Ω, drop = 25 × 0.0924 = 2.31 V (1.0% of 230 V).
Q7. A 40 A load is fed by a 30 m run of 10 mm² copper cable (1.83 Ω/km). What is the voltage drop?
- (a) 2.20 V
- (b) 4.39 V
- (c) 8.78 V
- (d) 1.10 V
Answer: (b) 4.39 V — loop R = 2 × 30 × 1.83 ÷ 1,000 = 0.110 Ω, drop = 40 × 0.110 = 4.39 V (1.9% of 230 V).
Q8. A 12 A load is fed by a 40 m run of 1.5 mm² copper cable (12.1 Ω/km). The drop is 11.62 V. Does this meet the 5% voltage-drop limit?
- (a) Yes, it is 3.2%
- (b) No, it is 5.1% and exceeds the 5% limit
- (c) Yes, it is 1.6%
- (d) No, it is 7.2%
Answer: (b) No, it is 5.1% and exceeds the 5% limit — loop R = 2 × 40 × 12.1 ÷ 1,000 = 0.968 Ω, drop = 12 × 0.968 = 11.62 V, and 11.62 ÷ 230 × 100 = 5.1%, so a larger cable is needed.
Q9. A 50 A load is fed by a 25 m run of 16 mm² copper cable (1.15 Ω/km). What is the voltage drop?
- (a) 1.44 V
- (b) 2.88 V
- (c) 5.75 V
- (d) 11.5 V
Answer: (b) 2.88 V — loop R = 2 × 25 × 1.15 ÷ 1,000 = 0.0575 Ω, drop = 50 × 0.0575 = 2.88 V (1.3% of 230 V).
Q10. A 32 A load is fed by an 18 m run of 6 mm² copper cable (3.08 Ω/km). What is the voltage drop?
- (a) 1.78 V
- (b) 3.55 V
- (c) 7.10 V
- (d) 0.89 V
Answer: (b) 3.55 V — loop R = 2 × 18 × 3.08 ÷ 1,000 = 0.111 Ω, drop = 32 × 0.111 = 3.55 V (1.5% of 230 V).
Also read: Voltage Drop Calculator | All MCQ Topics