Cable Types MCQs — Set 5
10 questions on how much current a cable can carry, and the grouping, temperature and installation factors that cut that rating down.
Q1. A 2.5 mm² twin and earth ring final circuit is normally protected by which MCB?
- (a) 6 A
- (b) 16 A
- (c) 32 A
- (d) 63 A
Answer: (c) 32 A — the standard UK ring final circuit uses 2.5 mm² cable on a 32 A MCB.
Q2. A 1.5 mm² lighting circuit is normally protected by which MCB?
- (a) 6 A
- (b) 32 A
- (c) 45 A
- (d) 63 A
Answer: (a) 6 A — the usual MCB for a 1.5 mm² domestic lighting circuit.
Q3. At an ambient temperature of 40 °C, the derating factor for 70 °C PVC cable is 0.87. What can a cable rated 20 A at 30 °C then carry?
- (a) 20 A
- (b) 17.4 A
- (c) 23 A
- (d) 8.7 A
Answer: (b) 17.4 A — 20 × 0.87 = 17.4 A, because the hotter surroundings leave less headroom before the insulation reaches 70 °C.
Q4. Four circuits bunched together have a grouping factor of 0.65. What can a cable rated 20 A on its own then carry?
- (a) 20 A
- (b) 13 A
- (c) 26 A
- (d) 6.5 A
Answer: (b) 13 A — 20 × 0.65 = 13 A, because the bunched cables heat each other.
Q5. A cable surrounded by thermal insulation for a long run has a derating factor of 0.5. What can a 20 A cable then carry?
- (a) 20 A
- (b) 10 A
- (c) 40 A
- (d) 5 A
Answer: (b) 10 A — 20 × 0.5 = 10 A, because the insulation traps the heat the cable produces.
Q6. Why must a cable’s rating be reduced (derated) when it is grouped with other cables?
- (a) The cables become magnetic
- (b) Heat cannot escape, so the insulation could exceed its temperature limit
- (c) The voltage rises
- (d) The copper oxidises
Answer: (b) Heat cannot escape, so the insulation could exceed its temperature limit — a cable’s rating is really a temperature limit.
Q7. Which installation method generally gives a cable its highest current rating?
- (a) Buried directly in the ground
- (b) Clipped direct on a wall in free air
- (c) Inside thermal insulation
- (d) Bunched in a conduit with five other circuits
Answer: (b) Clipped direct on a wall in free air — heat escapes freely, so the cable can carry its full tabulated rating.
Q8. A 6 mm² cooker circuit is commonly protected by which MCB?
- (a) 6 A
- (b) 16 A
- (c) 32 A
- (d) 100 A
Answer: (c) 32 A — the common MCB size for a 6 mm² domestic cooker circuit.
Q9. A cable buried in the ground is usually rated lower than the same cable clipped direct because why?
- (a) The soil is magnetic
- (b) Heat escapes more slowly into soil than into free air, and soil temperature and depth matter
- (c) The cable gets wet
- (d) Earthworms damage it
Answer: (b) Heat escapes more slowly into soil than into free air, and soil temperature and depth matter — so buried ratings use soil derating factors.
Q10. Which size carries the most current, all else being equal?
- (a) 1.5 mm²
- (b) 2.5 mm²
- (c) 4 mm²
- (d) 6 mm²
Answer: (d) 6 mm² — the larger cross-section has lower resistance and more surface to lose heat, so it carries the most current.
Also read: Home Load Calculator | All MCQ Topics