Busbar MCQs — Set 9

10 practice questions on busbar maintenance and thermography — finding hot spots before they fail.

Q1. What is thermography (infrared scanning) used for on busbars?

  • (a) To measure the busbar voltage
  • (b) To find hot joints and overloaded bars without switching anything off
  • (c) To paint the busbar
  • (d) To cut the busbar to size

Answer: (b) To find hot joints and overloaded bars without switching anything off — an IR camera sees the heat pattern, so a failing joint shows up as a hot spot while the plant keeps running.

Q2. During an IR scan, one phase of a busbar runs 20 °C hotter than the other two phases carrying the same load. What should be done?

  • (a) Ignore it — all phases always differ
  • (b) Investigate it at the next shutdown, as it points to a high-resistance joint or uneven loading
  • (c) Switch the plant off immediately without any plan
  • (d) Paint the hot phase a different colour

Answer: (b) Investigate it at the next shutdown, as it points to a high-resistance joint or uneven loading — a large temperature difference between identical phases is a classic sign of a bad joint, and it should be checked before it fails.

Q3. Which visual sign on a busbar suggests it has been overheating?

  • (a) Bright shiny copper
  • (b) Discolouration, darkened or burnt marks near a joint
  • (c) A clean, dust-free surface
  • (d) The maker’s label still attached

Answer: (b) Discolouration, darkened or burnt marks near a joint — heat oxidises and darkens copper, so burnt or discoloured metal around a joint is evidence of past overheating.

Q4. Why must dust and contamination be cleaned off busbars and insulators?

  • (a) Dust makes the busbar heavier
  • (b) Dust and moisture on insulator surfaces can cause tracking and flashover
  • (c) Dust increases the current rating
  • (d) Dust is only a cosmetic problem

Answer: (b) Dust and moisture on insulator surfaces can cause tracking and flashover — a dirty, damp insulator surface leaks current across it, which can track, carbonise and eventually flash over.

Q5. How often is infrared thermography typically carried out on switchboard busbars?

  • (a) Never — it is not useful
  • (b) Once a year as part of planned preventive maintenance
  • (c) Every hour
  • (d) Only after a fire

Answer: (b) Once a year as part of planned preventive maintenance — annual IR surveys under normal load are the usual routine, with more frequent checks for critical or problem boards.

Q6. A three-phase load draws 40 kW at 400 V with a power factor of 0.85. What current does the busbar carry during the thermal survey?

  • (a) 67.9 A
  • (b) 47.1 A
  • (c) 100 A
  • (d) 57.7 A

Answer: (a) 67.9 A — I = P ÷ (√3 × V × pf) = 40,000 ÷ (1.732 × 400 × 0.85) = 40,000 ÷ 589 = 67.9 A; thermography is most useful when the board is carrying a good load.

Q7. What test checks the insulation of a busbar system after cleaning or repair?

  • (a) A micro-ohmmeter test
  • (b) An insulation resistance (megger) test between phases and to earth
  • (c) A weighing test
  • (d) A paint thickness test

Answer: (b) An insulation resistance (megger) test between phases and to earth — the megger applies a high DC voltage and measures leakage resistance, proving the insulation is sound before re-energising.

Q8. Why must busbars be de-energised before cleaning or re-tightening joints?

  • (a) Because cleaning is only allowed at night
  • (b) Because the bars are live bare conductors — touching them or a tool slipping across phases is fatal
  • (c) Because the bars cool down when switched off
  • (d) Because cleaning works better in the dark

Answer: (b) Because the bars are live bare conductors — touching them or a tool slipping across phases is fatal — busbar work is done dead, isolated, proved dead and earthed where required, before hands or tools go near the bars.

Q9. Why are baseline thermal images kept from the first IR survey of a switchboard?

  • (a) They are needed for insurance paperwork only
  • (b) Later surveys are compared with the baseline, so a joint that is slowly getting hotter is caught early
  • (c) Baseline images make the bars run cooler
  • (d) They are never used again

Answer: (b) Later surveys are compared with the baseline, so a joint that is slowly getting hotter is caught early — trending temperatures against the original survey shows gradual deterioration that a single reading would miss.

Q10. Which tool is used to re-tighten busbar joint bolts to the correct value during maintenance?

  • (a) A torque wrench, set to the maker’s specified torque
  • (b) An ordinary spanner tightened as hard as possible
  • (c) A hammer
  • (d) A screwdriver

Answer: (a) A torque wrench, set to the maker’s specified torque — correct torque gives the right contact pressure; guessing with a spanner risks a loose or crushed joint.

Also read: Electrical Safety MCQs | All MCQ Topics