Busbar MCQs — Set 7
10 practice questions on short-circuit forces and withstand ratings — the forces that bend busbars in a fault.
Q1. How does the electromagnetic force between two parallel busbars change with the fault current?
- (a) Force is proportional to the current
- (b) Force is proportional to the square of the current
- (c) Force does not depend on the current
- (d) Force is inversely proportional to the current
Answer: (b) Force is proportional to the square of the current — the force between current-carrying bars grows with I², so fault currents produce enormous forces.
Q2. If the short-circuit current through a busbar doubles, what happens to the force on the bars?
- (a) It doubles
- (b) It stays the same
- (c) It quadruples
- (d) It halves
Answer: (c) It quadruples — force ∝ I², so doubling the current gives 2² = 4 times the force.
Q3. If the short-circuit current triples, by how much does the force on the busbars increase?
- (a) 3 times
- (b) 6 times
- (c) 9 times
- (d) 27 times
Answer: (c) 9 times — force ∝ I², so tripling the current gives 3² = 9 times the force.
Q4. If the fault current is halved by a current-limiting device, what happens to the force on the busbars?
- (a) It halves
- (b) It drops to one-quarter
- (c) It stays the same
- (d) It doubles
Answer: (b) It drops to one-quarter — force ∝ I², so half the current gives (1/2)² = 1/4 of the force.
Q5. How does the force between two busbars change if the spacing between them is doubled?
- (a) The force doubles
- (b) The force halves
- (c) The force stays the same
- (d) The force quadruples
Answer: (b) The force halves — the electromagnetic force between parallel conductors is inversely proportional to their spacing, so wider spacing means less force.
Q6. What does a busbar short-circuit rating written as “50 kA for 1 second” mean?
- (a) The busbar can carry 50 kA continuously
- (b) The busbar can survive a 50 kA fault for 1 second without damage from heating
- (c) The busbar trips at 50 kA after 1 second
- (d) The busbar melts at exactly 50 kA
Answer: (b) The busbar can survive a 50 kA fault for 1 second without damage from heating — this is the thermal (I²t) withstand rating, the fault energy the bar can absorb before the protection clears it.
Q7. In a three-phase short circuit, which phase’s busbar experiences the greatest electromagnetic force?
- (a) The middle phase, because it is pulled from both sides
- (b) The outer phases, because they are longest
- (c) All three phases feel exactly the same force
- (d) The neutral bar
Answer: (a) The middle phase, because it is pulled from both sides — the centre bar sits between two bars carrying current in the opposite half-cycle, so the forces on it add up to the maximum.
Q8. A three-phase load draws 150 kW at 400 V with a power factor of 0.8. What normal current flows in the busbar?
- (a) 180.4 A
- (b) 270.6 A
- (c) 339.6 A
- (d) 187.5 A
Answer: (b) 270.6 A — I = P ÷ (√3 × V × pf) = 150,000 ÷ (1.732 × 400 × 0.8) = 150,000 ÷ 554 = 270.6 A; note this normal load current is far smaller than a short-circuit current of tens of kA.
Q9. What is the difference between the peak (dynamic) withstand and the thermal withstand of a busbar?
- (a) They are the same thing
- (b) Peak withstand is about surviving the maximum mechanical force, while thermal withstand is about surviving the heating over the fault duration
- (c) Peak withstand applies only to aluminium bars
- (d) Thermal withstand applies only at low voltage
Answer: (b) Peak withstand is about surviving the maximum mechanical force, while thermal withstand is about surviving the heating over the fault duration — the bar must be strong enough not to bend at the first current peak, and thick enough not to overheat before the breaker clears.
Q10. Why is busbar bracing checked as carefully as the bar size itself?
- (a) Bracing only holds the paint on
- (b) Even a correctly sized bar can bend, clash or break its supports if the bracing cannot hold the peak fault force
- (c) Bracing increases the load current
- (d) Bracing replaces the need for circuit breakers
Answer: (b) Even a correctly sized bar can bend, clash or break its supports if the bracing cannot hold the peak fault force — supports and bracing carry the mechanical load of the fault, so they are part of the short-circuit rating.