Busbar MCQs — Set 4
10 practice questions on busbar current ratings, temperature rise, derating and heat — the numbers that size a busbar.
Q1. A copper busbar is commonly allowed a temperature rise of 65 K above a 40 °C ambient. What is its maximum permitted temperature?
- (a) 65 °C
- (b) 105 °C
- (c) 40 °C
- (d) 150 °C
Answer: (b) 105 °C — maximum temperature = ambient + rise = 40 + 65 = 105 °C; above this the bar, joints and nearby insulation are at risk.
Q2. A three-phase load draws 100 kW at 400 V with a power factor of 0.8. What current must the busbar carry continuously?
- (a) 90.2 A
- (b) 125 A
- (c) 180.4 A
- (d) 250 A
Answer: (c) 180.4 A — I = P ÷ (√3 × V × pf) = 100,000 ÷ (1.732 × 400 × 0.8) = 100,000 ÷ 554 = 180.4 A.
Q3. If the current through a busbar doubles, what happens to the I²R heat produced in it?
- (a) It doubles
- (b) It stays the same
- (c) It quadruples
- (d) It halves
Answer: (c) It quadruples — heat depends on current squared, so doubling the current makes 2² = 4 times the heat, which is why overloads overheat busbars fast.
Q4. Why is the current rating of a busbar lower inside an enclosed panel than in open air?
- (a) The enclosure traps heat, so the bar reaches its temperature limit at a lower current
- (b) Enclosed bars are made of thinner metal
- (c) The enclosure blocks the current
- (d) Enclosed panels always use aluminium bars
Answer: (a) The enclosure traps heat, so the bar reaches its temperature limit at a lower current — ratings assume a given cooling condition, and a closed box with poor ventilation derates the bar.
Q5. What does “derating” a busbar mean?
- (a) Reducing its permitted current because of high ambient temperature, grouping or poor ventilation
- (b) Increasing its current rating
- (c) Replacing copper with aluminium
- (d) Painting the busbar black
Answer: (a) Reducing its permitted current because of high ambient temperature, grouping or poor ventilation — when cooling is worse than the standard test condition, the safe continuous current must be lowered.
Q6. Why are busbars sometimes painted black instead of being left bright copper?
- (a) Black paint stops all corrosion
- (b) A dull black surface radiates heat better, slightly raising the current rating
- (c) Black paint increases the conductivity of copper
- (d) Black bars need no insulators
Answer: (b) A dull black surface radiates heat better, slightly raising the current rating — bright metal is a poor radiator of heat, while a matt black finish gives off heat more effectively.
Q7. A three-phase load draws 75 kW at 400 V with a power factor of 0.8. What busbar current is needed?
- (a) 90.2 A
- (b) 135.3 A
- (c) 180.4 A
- (d) 108.3 A
Answer: (b) 135.3 A — I = P ÷ (√3 × V × pf) = 75,000 ÷ (1.732 × 400 × 0.8) = 75,000 ÷ 554 = 135.3 A.
Q8. Where does a busbar system usually run hottest?
- (a) In the middle of a long straight run
- (b) At the bolted joints, where contact resistance adds extra heat
- (c) At the support insulators
- (d) At the earthed metal enclosure
Answer: (b) At the bolted joints, where contact resistance adds extra heat — joints have higher resistance than the plain bar, so they are the usual hot spots and the first place a thermal camera looks.
Q9. What is the difference between a busbar’s continuous rating and its short-time rating?
- (a) There is no difference
- (b) The continuous rating is the current it can carry for hours, while the short-time rating is the fault current it can survive for a second or so
- (c) The short-time rating is always lower than the continuous rating
- (d) The continuous rating applies only to aluminium bars
Answer: (b) The continuous rating is the current it can carry for hours, while the short-time rating is the fault current it can survive for a second or so — a busbar is sized for both: steady load current and the brief, huge short-circuit current.
Q10. Which factor does NOT reduce the safe current rating of a busbar?
- (a) High ambient temperature
- (b) Several bars grouped close together
- (c) Good ventilation and spacing between bars
- (d) Mounting inside a sealed enclosure
Answer: (c) Good ventilation and spacing between bars — ventilation and spacing improve cooling and raise the rating, while heat, grouping and sealed enclosures all lower it.