Busbar MCQs — Set 4

10 practice questions on busbar current ratings, temperature rise, derating and heat — the numbers that size a busbar.

Q1. A copper busbar is commonly allowed a temperature rise of 65 K above a 40 °C ambient. What is its maximum permitted temperature?

  • (a) 65 °C
  • (b) 105 °C
  • (c) 40 °C
  • (d) 150 °C

Answer: (b) 105 °C — maximum temperature = ambient + rise = 40 + 65 = 105 °C; above this the bar, joints and nearby insulation are at risk.

Q2. A three-phase load draws 100 kW at 400 V with a power factor of 0.8. What current must the busbar carry continuously?

  • (a) 90.2 A
  • (b) 125 A
  • (c) 180.4 A
  • (d) 250 A

Answer: (c) 180.4 A — I = P ÷ (√3 × V × pf) = 100,000 ÷ (1.732 × 400 × 0.8) = 100,000 ÷ 554 = 180.4 A.

Q3. If the current through a busbar doubles, what happens to the I²R heat produced in it?

  • (a) It doubles
  • (b) It stays the same
  • (c) It quadruples
  • (d) It halves

Answer: (c) It quadruples — heat depends on current squared, so doubling the current makes 2² = 4 times the heat, which is why overloads overheat busbars fast.

Q4. Why is the current rating of a busbar lower inside an enclosed panel than in open air?

  • (a) The enclosure traps heat, so the bar reaches its temperature limit at a lower current
  • (b) Enclosed bars are made of thinner metal
  • (c) The enclosure blocks the current
  • (d) Enclosed panels always use aluminium bars

Answer: (a) The enclosure traps heat, so the bar reaches its temperature limit at a lower current — ratings assume a given cooling condition, and a closed box with poor ventilation derates the bar.

Q5. What does “derating” a busbar mean?

  • (a) Reducing its permitted current because of high ambient temperature, grouping or poor ventilation
  • (b) Increasing its current rating
  • (c) Replacing copper with aluminium
  • (d) Painting the busbar black

Answer: (a) Reducing its permitted current because of high ambient temperature, grouping or poor ventilation — when cooling is worse than the standard test condition, the safe continuous current must be lowered.

Q6. Why are busbars sometimes painted black instead of being left bright copper?

  • (a) Black paint stops all corrosion
  • (b) A dull black surface radiates heat better, slightly raising the current rating
  • (c) Black paint increases the conductivity of copper
  • (d) Black bars need no insulators

Answer: (b) A dull black surface radiates heat better, slightly raising the current rating — bright metal is a poor radiator of heat, while a matt black finish gives off heat more effectively.

Q7. A three-phase load draws 75 kW at 400 V with a power factor of 0.8. What busbar current is needed?

  • (a) 90.2 A
  • (b) 135.3 A
  • (c) 180.4 A
  • (d) 108.3 A

Answer: (b) 135.3 A — I = P ÷ (√3 × V × pf) = 75,000 ÷ (1.732 × 400 × 0.8) = 75,000 ÷ 554 = 135.3 A.

Q8. Where does a busbar system usually run hottest?

  • (a) In the middle of a long straight run
  • (b) At the bolted joints, where contact resistance adds extra heat
  • (c) At the support insulators
  • (d) At the earthed metal enclosure

Answer: (b) At the bolted joints, where contact resistance adds extra heat — joints have higher resistance than the plain bar, so they are the usual hot spots and the first place a thermal camera looks.

Q9. What is the difference between a busbar’s continuous rating and its short-time rating?

  • (a) There is no difference
  • (b) The continuous rating is the current it can carry for hours, while the short-time rating is the fault current it can survive for a second or so
  • (c) The short-time rating is always lower than the continuous rating
  • (d) The continuous rating applies only to aluminium bars

Answer: (b) The continuous rating is the current it can carry for hours, while the short-time rating is the fault current it can survive for a second or so — a busbar is sized for both: steady load current and the brief, huge short-circuit current.

Q10. Which factor does NOT reduce the safe current rating of a busbar?

  • (a) High ambient temperature
  • (b) Several bars grouped close together
  • (c) Good ventilation and spacing between bars
  • (d) Mounting inside a sealed enclosure

Answer: (c) Good ventilation and spacing between bars — ventilation and spacing improve cooling and raise the rating, while heat, grouping and sealed enclosures all lower it.