AC Fundamentals MCQs — Set 6

10 practice questions on power factor, real versus apparent power and power factor correction — with answers and full working.

Q1. Power factor is the ratio of which two quantities?

  • (a) Real power (kW) to apparent power (kVA)
  • (b) Apparent power (kVA) to real power (kW)
  • (c) Reactive power (kVAR) to real power (kW)
  • (d) Real power (kW) to reactive power (kVAR)

Answer: (a) Real power (kW) to apparent power (kVA) — pf = kW ÷ kVA = cos φ.

Q2. A load draws 25 kVA at a power factor of 0.8. What is its real power?

  • (a) 15 kW
  • (b) 20 kW
  • (c) 25 kW
  • (d) 31.25 kW

Answer: (b) 20 kW — kW = kVA × pf = 25 × 0.8 = 20 kW.

Q3. A load draws 200 kVA at a power factor of 0.8. What is its real power?

  • (a) 120 kW
  • (b) 160 kW
  • (c) 200 kW
  • (d) 250 kW

Answer: (b) 160 kW — kW = kVA × pf = 200 × 0.8 = 160 kW.

Q4. Which device is commonly used to improve the power factor of an inductive load?

  • (a) Inductor
  • (b) Capacitor bank
  • (c) Resistor
  • (d) Transformer

Answer: (b) Capacitor bank — capacitors supply leading reactive power that cancels the lagging reactive power of inductive loads.

Q5. What is the power factor of a pure inductor?

  • (a) 1
  • (b) 0 lagging
  • (c) 0 leading
  • (d) 0.5 lagging

Answer: (b) 0 lagging — in a pure inductor the current lags voltage by 90°, so cos 90° = 0.

Q6. What is the power factor of a pure capacitor?

  • (a) 1
  • (b) 0 lagging
  • (c) 0 leading
  • (d) 0.5 leading

Answer: (c) 0 leading — in a pure capacitor the current leads voltage by 90°, so cos 90° = 0, leading.

Q7. A load draws 100 kVA at a power factor of 0.6. What are its real and reactive powers?

  • (a) 60 kW and 80 kVAR
  • (b) 80 kW and 60 kVAR
  • (c) 100 kW and 60 kVAR
  • (d) 60 kW and 100 kVAR

Answer: (a) 60 kW and 80 kVAR — kW = 100 × 0.6 = 60, kVAR = 100 × 0.8 = 80.

Q8. A load has an apparent power of 10 kVA and a real power of 8 kW. What is its power factor?

  • (a) 0.6
  • (b) 0.8
  • (c) 1.25
  • (d) 0.5

Answer: (b) 0.8 — pf = kW ÷ kVA = 8 ÷ 10 = 0.8.

Q9. For the same kW load, what does a lower power factor mean for the supply current?

  • (a) Lower current
  • (b) Higher current
  • (c) The same current
  • (d) No current at all

Answer: (b) Higher current — I = kW ÷ (V × pf), so a smaller pf forces a larger current for the same real power.

Q10. A 1,150 W load runs on a 230 V supply at a power factor of 0.5. What current does it draw?

  • (a) 5 A
  • (b) 10 A
  • (c) 2.5 A
  • (d) 20 A

Answer: (b) 10 A — I = P ÷ (V × pf) = 1,150 ÷ (230 × 0.5) = 1,150 ÷ 115 = 10 A.

Also read: Watt Calculator | All MCQ Topics